77mm
35mm
• 35x77mm size.
• On-Off control.
• Relay output for cooling or heating control.
Alarm Relay
• Single NTC probe input
• Range -60 to 150°C
• Ideal for industrial or commercial applications
• Probe failure setting, output status can be set to
ON, OFF or pulse.
• Sensor input offset setting.
• Selectable heating or cooling control
• Selectable independent, deviation and
band alarm types.
• 0000 or 000.0 units display.
• Temperature units °C or °F.
• CE marked.
1241055 & 1241056 is intended for installation within control panels. Make sure that the device is used only for
intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the
cables that are connected to the device must be free of electrical power. The device must be protected against
inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded.
All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables.
These cables should not be close to the power cables or components. The installation and electrical connections must
be carried out by a qualified staff and must be according to the relevant locally applicable regulations.
CONNECTION DIAGRAM
Holding screw
0.4-0.5Nm.
Equipment is protected throughout
by DOUBLE INSULATION
5
6
SUPPLY:
NOTE:
184-253V AC
50/60Hz 3VA
Line
Neutral
230V AC
Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
1 / 2
230V AC +%10 -%20, 50/60Hz or 24V AC/DC %10
Max. 5VA
Power connector : 2.5mm² screw-terminal, Signal connector : 1,5mm² screw-terminal conenction.
EN 61326-1: 2013 (Performance criterion B is satisfied for EN 61000-4-3)
EEPROM (Min. 10 years)
Max. 100ohm
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
12 bit resolution, 100ms sampling time.
Max. 2000m
Do not use the device in locations subject to corrosive and flammable gasses.
Max. humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.
0 ... +50 /
-25... +70
°C °C(without icing)
According to EN60529; Front panel: IP65 Rear panel : IP20
Scale Range
Accuracy
EN 60751
-60.0...150.0 °C -76.0...302.0°F
± 1% (for full scale) ±
1 Digit
Supply
HOUSING
Housing Type
Dimensions
Weight
Enclosure Materials
CONTROL
Control Type
Control Algorithm
A/D Converter
Hysteresis
INPUT
Height
Ambient/Storage temperature
Relative Humidity
Protection Class
Input Type
NTC Sensor Resistance
61mm
5mm
2
Connection
Cable
Panel
Rubber
Packing
71,5mm
1
29,5mm
250V AC, 8A (for resistive load), NO and NC control output.
OUTPUT
Life Expectancy for Relay
C1 Output
TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
ELECTRICAL CHARACTERISTICS
Power Consumption
Wiring
Indicator
EMC
Safety Requirements
Data Retention
Line Resistance
4 digits, 12.5mm, 7 segment red LED
Single-setpoint and alarm control.
Adjustable between 0.1 and 20.0°C/F.
Suitable for flush-panel mounting according to DIN 43 700.
H35xW77xD61mm
Approx. 215g (After packing)
Self extinguishing plastics
While cleaning the device, solvents (thinner, gasoline, acid etc.) or corrosive materials must not be used.
Dimensions
For removing mounting clamps:
- Push the flush-mounting clamp
in direction 1 as shown in the
figure below.Then,pull
out the clamp in direction 2 .
Depth
Flush mounting
clamp
Flush mounting
clamp
Panel cut-out
Note:
1) Panel thickness should
be maximum 7mm.
2) If there is not 60mm free
space at the back side of
the device,it would be
difficult to remove it from
the panel.
30.000.000 Switching for no-load operation; 300.000 switching for 8A resistive load at 250VAC.
1241055/56-E-01-161006
A1 Output
250V AC, 8A (for resistive load), NO control output.
FOR MORE INFORMATION VISIT THIS SITE
http://www.rs-components.com/index.html
EN
Pl
ea
se
re
ad
thi
s
doc
um
e
nt
ca
re
fu
ll
y
be
fo
re
u
s
i
ng
thi
s
produ
ct.
T
h
e
guar
an
te
e w
il
l
b
e i
n
va
l
i
da
te
d i
f
t
h
e
d
ev
i
c
e
i
s
d
am
a
g
ed
b
y
no
t
fo
l
lo
wi
ng
ins
t
ruc
t
i
on
s
det
ai
l
ed
i
n
the ma
n
ua
l
.
T
he
c
ompa
ny
s
h
al
l
n
ot b
e
r
e
s
p
o
ns
i
b
le
f
o
r
an
y
dam
a
ge
o
r
los
s
es
h
owe
v
er
c
au
se
d
,
w
h
ic
h
may
b
e
ex
per
ienc
ed
a
s
a re
su
l
t
of
th
e i
n
s
t
al
l
at
io
n
or
u
s
e
of
t
hi
s
p
ro
duc
t.
Instruction Manual
RS Pro 35 x 77mm ON/OFF Thermostat, NTC, Two Outputs
Stock Number: 124-1055, 124-1056
SET
°C
SET
°F
C1
A1
SET
°C
SET
°F
C1
A1
230V AC +10% -20%
50/60Hz 5VA
250V AC 8A
RESISTIVE LOAD
1 2 3 4 5 6
7 8 9
10
11
12
NTC
C1
A1
1
1241056
DIGITAL
THERMOSTAT
Made In Turkey
250V AC 8A
RESISTIVE LOAD
1 2 3 4 5 6
7 8 9
10
11
12
NTC
24V AC/DC ±10%
50/60Hz 5VA
C1
A1
1
1241055
DIGITAL
THERMOSTAT
Made In Turkey
230V AC +10% -20%
50/60Hz 5VA
250V AC 8A
RESISTIVE LOAD
1 2 3 4 5 6
7 8 9
10
11
12
NTC
C1
A1
1
1241056
DIGITAL
THERMOSTAT
Made In Turkey
124-1055
124-1056
2
2
When s.co. = 0 , if key is
pressed for 4 seconds while
holding down key, then
d.PAr. is seen on display and the
device is returned to factory
settings.
SET
SET
A1.ty = Alarm type selection.
Please see A1 Output Format Table for
settings.
a1..sc. = A1.Cn. Security menu access
level
nonE = Invisible.
P.yEs = Can be modified.
P. no = Visible but can’t be modified.
A.1.L.L.
A1.H.L.
A1.ty.
A1.Hy.
oFFs.
C.tyP.
Unit.
d.P.
C1.Cn. A1.Cn. ConF.
SECu.
S.Cod.
C1.sc.
A1..sc.
Co..sc.
C.S.sc.
A.S.sc.
SET SET SET
SET
Programming Menu
Default
Value
-60
P.YES
P.YES
P.YES
P.YES
P.YES
0
150
in.A.L.
2
HEAt
°C
no
0
Programming Diagram
SET
100
110
SET
When this button is pressed
C.SEt message is appeared
and temperature setpoint
adjustment mode is entered.
Measured temperature
C1 Set value
A1 Set value
105 C1.SE.
A1.SE.
101
111
102
112
101
111
Default value
100
110
If no key is pressed within 3 seconds, Running Mode is entered.
Running Mode
A1 OUTPUT FORMATS
Independent Alarm
A1.ty.=in.A.l.
A1.ty.=in.A.H.
Deviation Alarm
A1.ty.= dE.a.l.
A1.ty.= dE.a.H.
Band Alarm
A1.ty.= bi.A.l.
A1.ty.= bi.A.H.
ASV
SV
SV
SV+ASV
SV+ASV
SV-ASV
OFF
OFF
OFF
OFF
OFF
OFF
-300
300
+300
300
ON
ON
ON
ON ON
ON
SV = C1 output setpoint ASV = A1 output setpoint
(ASV Min. =-300, ASV Max. = +300)
(ASV Min. = 0, ASV Max. = +300)
(ASV Min. = Beginning of Scale
ASV Max. = End of Scale)
SV =C1 output setpoint ASV = A1 output setpoint
a1,Hy.
A1.Hy.
A1.Hy.
A1.Hy.
SET
C1.E.S.
A1.E.S.
off
off
Temperature setpoint value is adjusted with buttons then,
when one of these buttons are pressed for the first time, blinking
setpoint value appears.
If no key is pressed within 3 seconds, Running Mode is entered.
Entering Running Mode in Programming Mode :
In Programmin Mode, if no keys are pressed for 20 seconds information is saved automatically
and Running Mode is entered. Alternatively, if and keys are pressed together,
Programming Menu is entered. In the Programming Menu, if key is pressed while holding
down key, then Running Mode is entered.
SET
If key is pressed while holding down key,
then Programming Menu is entered.
C1.Hy. = Output hysteresis value.
It can be adjusted between 0.1 and
20.0 °C.
C1..L.L.
C1..H.L.
C1.Hy.
Default
Value
-60
150
2
C1..L.L.= Control set point lower limit
for C1 output.
It can be adjusted between -60.0 and
C1.H.L. parameter value.
C1H.L.= Control set point upper limit
for C1 output.
It can be adjusted between 150.0 and
C1.L.L. parameter value.
S.Cod = Access code for security menu.
This parameter should be 412 .
SET
C1..sc. = C1,Cn. Security menu access
level.
nonE = Invisible.
P.yEs = Can be modified.
P. no = Visible but can’t be modified.
..Co.sc. = ConF. Configuration menu
access level.
nonE = Invisible.
P.yEs = Can be modified.
P. no = Visible but can’t be modified.
C.S.sc. = C1 set value security access
level.
P.yEs = Can be modified.
P. no = Visible but can’t be modified.
C.S.sc. = Alarm set value security access
level.
P.yEs = Can be modified.
P. no = Visible but can’t be modified.
C.typ. = Control type selection.
C.typ. = HEAt Heating control is selected.
C.typ. = CooL Cooling control is selected.
Unit = Temperature unit selection.
Unit. = Can be selected as °C or °F
d.P. = Decimal point display selection.
If d.P.. = no , decimal value is not dotted.
If d.P. = YES , decimal value is dotted.
oFFS. = Offset value.
Zero point shift value is added to the
measured value. This feature is used for
eliminating the measuring probe distance
errors. It can be adjusted between -20.0 and
20.0°C.
C1.E.S. = C1 Output state in case of sensor
failure.
on = Output is ON in case of sensor
failure.
off = Output is OFF in case of sensor
failure.
A1..L.L.= Control set point lower limit for
A1 output.
It can be adjusted between -60.0 and
A1.H.L. parameter value.
A1H.L.= Control set point upper limit for
A1 output.
It can be adjusted between 150.0 and
A1.L.L. parameter value.
A1.Hy. = A1çıkışı histerisiz değeri.
0.1 ile 20.0 °C arasında ayarlanabilir.
A1.E.S. = A1 Output state in case of
sensor failure.
on = Output is ON in case of sensor
failure.
off = Output is OFF in case of sensor
failure.
Default
Value
Default
Value
ERROR MESSAGES
pfa
____
Sensor is broken
Temperature value is
higher than the scale
Temperature value is
lower than the scale
----
Modification Of Parameter Diagram
While holding down key, parameter value blinks and by
using keys, the requested value can be adjusted.
Chys
6
5
6
SET
SET SET
SET
If key is pressed and held 0.6 seconds, the value of the
selected parameter increases rapidly. If waited enough,the
value increases a hundred at each step. After 1 second,
following the release of the key, initial increasing condition is
returned. The same procedure is valid for the decrementing.
1241055/56-E-01-161006
2 / 2