Automated Logic’s line of intelligent sensors includes the RS Standard, RS Plus, RS Pro and RS Pro F and is
designed for use with the ZN, SE, ME line controllers and Room Controller. The RS Plus offers a local set point
adjustment and override to an occupied mode and LED indication of current status. The RS Pro has a large LCD
display and easy-to-use occupant controls. The RS Pro F includes additional functions ideal for fan coil units
operating with multiple fan speeds. All sensors provide precision measurement and communication capabilities
in attractive low profile enclosures. A hidden communications jack provides local access to the HV-ac control
system for commissioning and maintenance.
Key Features and Benefits
All Room Sensors:
Attractive, low profile enclosure in a neutral color complements any room.
Precise 10K ohm thermistor with + 0.36ºF (0.2ºC) standard accuracy and less than 0.18ºF (0.01ºC) drift over
a ten year span – requires no maintenance or re-calibration.
A hidden communication port allows a laptop computer to be connected to the HV-ac Control System.
Multiple RS room sensors can be daisy-chained to one controller for temperature averaging or high/low
select control. (One RS Plus, RS Pro or RS Pro F with up to four RS Standards.)
Mounts on a standard 2” by 4” electrical box for easy installation.
RS Plus:
Features a convenient local setpoint adjustment through an easy to use slide potentiometer.
Occupancy override is simple using the momentary push button on the RS Plus with a bright LED for
immediate indication of status. When the override button is pressed during an unoccupied mode, the zone
reverts to an occupied setpoint for a predeterminded period of time.
RS Pro/RS Pro F:
Large, easy-to-read LCD on the RS Pro displays zone temperature, outside air temperature, heating setpoint,
cooling setpoint, and local override (after-hours occupancy) time.
Occupancy override is easy using the “Manual Onmomentary pushbutton on the RS Pro. A single push
switches the zone to an Occupied mode for a preset period of time. Multiple pushes increase the override
time, and the LCD displays precisely how long the zone will stay occupied. The occupied time per push and
maximum override time are fully programmable in EIKON
®-
LogicBuilder.
Zone setpoints can be easily changed on the RS Pro by pressing the “Warmer” or “Coolerbutton.
How much each push affects the setpoint and the maximum total adjustments are fully programmable in
EIKON-LogicBuilder.
Pressing the “Fan Speed” button on the RS Pro F incrementally
adjusts the fan speed of the fan coil unit. The “Mode” button can be
used to select among several zone operation modes as programmed
in EIKON-LogicBuilder.
RS
Intelligent Room Sensors
RS Standard
RS Plus
RS Pro
RS Pro F
LGR Router
or ME-LGR
Router/Controller
To
Third Party
Equipment
BACnet
®
/IP, 100Base-T Ethernet
Ethernet, ARCNET, EIA-485, EIA-232
XML/SOAP
HTML/HTTP
BACnet MS/TP, ARCNET
WML/WAP WML/WAP
HTML/HTTP
Internet
Server
Enterprise System
Web Browser
Cell
Phone
Web Browser
PDA
ME line
Controller
SE line
Controller
Room Sensor
Room Sensor
ZN line
Controller
Room Sensor
Room
Controller
ME
812
u-E
Controller
RS
Specifications
Communication: 115 kbaud Rnet
Power: ZN, SE, or ME line Controllers
Sensing Element: Precision Thermistor. Standard accuracy ±0.35°F (0.2°C). Less than ±0.18°F (0.1°C)
drift over a 10 year period.
Wiring: Remote mounting up to 500 ft. is via four conductor shielded cables - 18 AWG if using
BACview on the Rnet, 22 AWG if using only RS sensors on the Rnet.
Local Access Port: 5 pin port for commissioning and maintenance.
Mounting: Standard 2” by 4” electrical box using 6-32 by 1/2” mounting screws provided.
Overall Dimensions: 2-3/4” (width) by 4-3/4” (height) by 5/8” (depth)
(depth is a maximum 15/16”).
70mm (width) by 120mm (height) by 16mm (depth)
(depth is a maximum 24mm).
Features* RS Standard RS Plus RS Pro RS Pro F
Low profile design, neutral color
Precise 10K ohm thermistor
Requires no maintenance or re-calibration
Hidden communication port
Can be daisy-chained to one controller
Mounts on a standard 2” by 4” electrical box
Convenient local setpoint adjustment
Simple occupancy override
Large, easy-to-read LCD
Easily changed zone setpoints
Fan speed control
*See Key Features and Benefits for specific details.
www.carrier.com.hk
© 2007, Automated Logic Corporation. Automated Logic, the Automated Logic logo, EIKON and WebCTRL are registered trademarks of Automated Logic Corporation.
BACnet is a registered trademark of ASHRAE. All other trademarks are the property of their respective owners. Specifications are subject to change without prior notice.