l
Installation, Start–Up, Operating and
Service and Maintenance Instructions
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 1 – Minimum Free Area Required for Each Combustion Air
opening of Duct to Outdoors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 2 – Minimum Space Volumes for 100% Combustion, Ventila-
tion, and Dilution from Indoors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 3 – Opening Dimensions - In. (mm). . . . . . . . . . . . . . . . . . . . 10
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 4 – Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . . . . 14
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 5 – Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 6 – Minimum Allowable Input Rating of
Space-Heating Appliance in Thousands of Btuh per Hour. . . . . . . . 22
Table 7 – Combined Appliance Maximum Input Rating
in Thousands of Btuh per Hour. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 8 Recommended Minimum Vent Height Per Furnace and Vent
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
START-UP, ADJUSTMENT, AND SAFETY CHECK . . . . . . . . . . . 26
Table 9 – Altitude Derate Multiplier for U.S.A.. . . . . . . . . . . . . . . . 27
Table 10 – Gas Rate (CU ft./hr) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 11 – Blower Off Delay Setup Switch . . . . . . . . . . . . . . . . . . . 29
Table 12 – Cooling Airflow Adjustments from 1.5 to 6 Tons . . . . . 30
Table 13 – Air Delivery - CFM (With Filter). . . . . . . . . . . . . . . . . . 31
Table 14 – Furnace Setup Switch Description . . . . . . . . . . . . . . . . . 35
Table 15 Orifice Size and Manifold Pressure (In. W.C.) for Gas Input
Rate (Tabulated Data Based on 22,000 Btuh High-Heat/14,500 Btuh
for Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft. (305 M)
Above Sea Level) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 16 Orifice Size and Manifold Pressure (In. W.C.) for Gas Input
Rate (Tabulated Data Based on 21,000 Btuh High-Heat/14,500 Btuh
for Low-Heat Per Burner, Derated 4 Percent for Each 1000 Ft. (305 M)
Above Sea level). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . . . 38
Table 17 – Filter Size Information - In. (mm) . . . . . . . . . . . . . . . . . 40
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . . . 50
EXAMPLE OF MODEL NUMBER . . . . . . . . . . . . . . . . . . . . . . . . . 50
TRAINING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Most states in the USA an jurisdictions in Canada have laws that require
the use of Carbon Monoxide (CO) alarms with fuel burning products.
Examples of fuel burning products are furnaces, boilers, space heaters,
generators, water heaters, stoves/ranges, clothes dryers, fireplaces,
incinerators, automobiles, and other internal combustion engines. Even
if there are no laws in your jurisdiction requiring a CO Alarm, it’s highly
recommended that whenever any fuel burning product is used in or
around the home or business that the dwelling be equipped with a CO
Alarm(s). The Consumer Product Safety Commission recommends the
use of CO Alarm(s). The CO Alarm(s) must be installed, operated, and
maintained according to the CO Alarm manufacturer’s instructions. For
more information about Carbon Monoxide, local laws, or to purchase a
CO Alarm online, please visit the following website.
https://www.kidde.com.
A200103
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
on the referenced subject, which is represented only by the standard in its entirety.
880TA/881TA
80% AFUE, Two-Stage, Variable–Speed
4–Way Multipoise, Non-Condensing Gas Furnace
Series A
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury and/or
death.
Carbon Monoxide (CO) is a colorless, odorless, and tasteless poisonous
gas that can be fatal when inhaled. Follow all installation, maintenance,
and service instructions. See additional information below regarding
the installation of a CO Alarm.
Use of the AHRI Certified TM Mark indicates
a manufacturer’s participation in the program.
For verification of certification for individual
products, go to www.ahridirectory.org .
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
A190045
Fig. 1 – Dimensional Drawing
FURNACE SIZE
A
CABINET WIDTH
B
OUTLET WIDTH
C
TOP AND
BOTTOM FLUE
COLLAR
D
BOTTOM
INLET WIDTH
VENT
CONNECTION
SIZE
SHIP WT.
LB (KG)
36045C17 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16 (406) 4 (102) 118 (53.5)
36070C14 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 118 (53.5)
48070C17 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16 (406) 4 (102) 126 (57.1)
60070C21 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 147 (66.7)
48090C17 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16 (406) 4 (102) 134 (60.8)
60090C21 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 153 (69.4)
60110C21 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 156 (70.7)
66135C24 24-1/2 (622) 22-7/8 (581) 15-1/16 (383) 23 (584)
4 (102)
*
*. 135 size furnace require a 5 or 6-in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete installation
requirements.
169 (76.6)
U.S. ECCN: Not Subject to Regulation (N.S.R.)
SD5523-4 REV. B
NOTE: ALL DIMENSIONS IN INCH (MM)
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas
and electrical components. Only trained and qualified personnel should
install, repair, or service heating equipment. Untrained personnel can
perform basic maintenance functions such as cleaning and replacing air
filters. All other operations must be performed by trained service
personnel. When working on heating equipment, observe precautions in
literature, on tags, and on labels attached to or shipped with furnace and
other safety precautions that may apply.
These instructions cover minimum requirements and conform to existing
national standards and safety codes. In some instances, these instructions
exceed certain local codes and ordinances, especially those that may not
have kept up with changing residential construction practices. We
require these instructions as a minimum for a safe installation.
Wear safety glasses, protective clothing and work gloves. Have fire
extinguisher available during start-up and adjustment procedures and
service calls.
This is the safety-alert symbol . When you see this symbol on the
furnace and in instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury or
death. WARNING signifies a hazard which could result in personal
injury or death. CAUTION is used to identify hazards which may result
in minor personal injury or product and property damage. NOTE is used
to highlight suggestions which will result in enhanced installation,
reliability, or operation.
The following additional safety considerations should be followed for
gas furnaces:
1. Use only with type of gas approved for this furnace. Refer to the
furnace rating plate.
2. Install this furnace only in a location and position as specified in the
“Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace
space as specified in “Air for Combustion and Ventilation” section.
4. Combustion products must be discharged outdoors. Connect this
furnace to an approved vent system only, as specified in the
“Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks
to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s intended
temperature-rise range with a duct system which has an external
static pressure within the allowable range, as specified in the
“Start-Up, Adjustments, and Safety Check” section. See furnace
rating plate.
7. When a furnace is installed so that supply ducts carry air circulated
by the furnace to areas outside the space containing the furnace, the
return air shall also be handled by duct(s) sealed to the furnace
casing and terminating outside the space containing the furnace.
See “Air Ducts” section.
8. A gas-fired furnace for installation in a residential garage must be
installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the
furnace installation and operation complies with the first
CAUTION in the LOCATION section of these instructions.
10. These Multipoise Gas-Fired Furnaces are CSA (formerly A.G.A.
and C.G.A.) design-certified for use with natural and propane gases
(see furnace rating plate) and for installation in alcoves, attics,
basements, closets, utility rooms, crawlspaces, and garages. The
furnace is factory-shipped for use with natural gas. A CSA (A.G.A.
and C.G.A.) listed accessory gas conversion kit is required to
convert furnace for use with propane gas.
11. See Fig. 2 for required clearances to combustible construction.
12. Maintain a 1-in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36 in. (914 mm) horizontally
from the furnace. See NFPA 90B or local code for further
requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile,
or any other combustible material other than wood flooring. In
downflow installations, factory accessory floor base MUST be used
when installed on combustible materials and wood flooring. Special
base is not required when this furnace is installed on manufacturer’s
Coil Assembly Part No. CNRV, CNPV, CAP, or CAR or when Coil
Box Part No. KCAKC is used. See Fig. 2 for clearance to
combustible construction information.
WARNING
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation,
personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or
use can cause carbon monoxide poisoning, explosion, fire, electrical
shock, or other conditions which may cause personal injury or property
damage. Consult a qualified service agency, local gas supplier, or your
distributor or branch for information or assistance. The qualified
service agency must use only factory-authorized and listed kits or
accessories when modifying this product.
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Application of this furnace should be indoors with special attention
given to vent sizing and material, gas input rate, air temperature rise,
unit leveling, and unit sizing.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts, and servicing furnaces.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
INTRODUCTION
A10269
Fig. 2 – Clearances to Combustibles
The 4-way multipoise Category I fan-assisted furnace is CSA (formerly
A.G.A. and C.G.A.) design-certified. A Category I fan-assisted furnace is
an appliance equipped with an integral mechanical means to either draw
or force products of combustion through the combustion chamber and/or
heat exchanger. The furnace is factory-shipped for use with natural gas.
This furnace is not approved for installation in mobile homes,
recreational vehicles, or outdoors.
This furnace is designed for minimum continuous return-air temperature
of 60°F (15°C) db or intermittent operation down to 55°F (13°C)db such
as when used with a night setback thermostat. Return-air temperature
must not exceed 80°F (27°C) db. Failure to follow these return-air
temperature limits may affect reliability of heat exchangers, motors, and
controls, see Fig. 3.
For accessory installation details, refer to the applicable instruction
literature.
NOTE: Remove all shipping brackets and materials before operating the
furnace.
A06745
Fig. 3 – Return Air Temperature
A02054
Fig. 4 – Prohibit Installation on Back
A93044
Fig. 5 – Installation in a Garage
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these
instructions. The installation must comply with regulations of the
serving gas supplier, local building, heating, plumbing, and other codes.
In absence of local codes, the installation must comply with the national
codes listed below and all authorities having jurisdiction.
In the United States, follow all codes and standards for the following:
Safety
NFPA 54/ANSI Z223.1 and the Installation Standards, Warm Air
Heating and Air Conditioning Systems ANSI/NFPA 90B.
General Installation
Current edition of the NFGC and the NFPA 90B. For copies, contact the
National Fire Protection Association Inc., Batterymarch Park, Quincy,
MA 02269; (www.NFPA.org) or for only the NFGC, contact the
American Gas Association, 400 N. Capitol Street, N.W., Washington,
DC 20001 (www.AGA.org.).
Combustion and Ventilation Air
Section 9.3 NFPA 54/ANSI Z223.1, Air for Combustion and Ventilation.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
Do not install the furnace on its back or hang furnace with control
compartment facing downward. Safety control operation will be
adversely affected. Never connect return-air ducts to the back of the
furnace, see Fig. 4.
60
80 / 27 C
/ 16 C
WARNING
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
When the furnace is installed in a residential garage, the burners and
ignition sources must be located at least 18 in. (457 mm) above the
floor. The furnace must be located or protected to avoid damage by
vehicles. When the furnace is installed in a public garage, airplane
hangar, or other building having a hazardous atmosphere, the furnace
must be installed in accordance with the NFPA 54/ANSI Z223.1, see
Fig. 5.
18-IN. (457.2 mm)
MINIMUM TO BURNERS
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
Duct Systems
Air Conditioning Contractors Association (ACCA) Manual D, Sheet
Metal and Air Conditioning Contractors National Association
(SMACNA), or American Society of Heating, Refrigeration, and Air
Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook
Chapter 34 or 2000 HVAC Systems and Equipment Handbook Chapters
9 and 16.
Acoustical Lining and Fibrous Glass Duct
Current edition of SMACNA and NFPA 90B as tested by UL Standard
181 for Class I Rigid Air Ducts.
Gas Piping and Gas Pipe Pressure Testing
NFPA 54/ANSI Z223.1; Chapters 5, 6, and 7 and National Plumbing
Codes.
Electrical Connections
National Electrical Code (NEC) ANSI/NFPA70.
Venting
NFPA 54/ANSI Z223.1; Chapters 12 and 13.
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
1. Disconnect all power to the furnace. Multiple disconnects may be
required. DO NOT TOUCH THE CONTROL OR ANY WIRE
CONNECTED TO THE CONTROL PRIOR TO DISCHARGING
YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person’s hand
during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control
or connecting wires as long as you do nothing to recharge your
body with static electricity (for example; DO NOT move or shuffle
your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with
static electricity), firmly touch a clean, unpainted metal surface of
the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge your
body’s electrostatic charge to ground to protect the control from
damage. If the control is to be installed in a furnace, follow items 1
through 4 before bringing the control or yourself in contact with the
furnace. Put all used and new controls into containers before
touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also
be used to prevent ESD damage.
LOCATION
GENERAL
This multipoise furnace is shipped in packaged configuration. Some
assembly and modifications are required when used in any of four
applications, see in Fig. 6.
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Electrostatic discharge can affect electronic components. Take
precautions during furnace installation and servicing to protect the
furnace electronic control. Precautions will prevent electrostatic
discharges from personnel and hand tools which are held during the
procedure. These precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control, and the
person at the same electrostatic potential.
CAUTION
!
PERSONAL INJURY AND/OR PROPERTY
DAMAGE HAZARD
Improper use or installation of this furnace may result in premature
furnace component failure. This gas furnace may be used for heating
buildings under construction provided that:
The furnace is permanently installed with all electrical wiring, piping,
venting and ducting installed according to these installation
instructions. A return air duct is provided, sealed to the furnace casing,
and terminated outside the space containing the furnace. This prevents
a negative pressure condition as created by the circulating air blower,
causing a flame rollout and/or drawing combustion products into the
structure.
The furnace is controlled by a thermostat. It may not be hot wired”
to provide heat continuously to the structure without thermostatic
control.
– Clean outside air is provided for combustion. This is to minimize the
corrosive effects of adhesives, sealers and other construction materials.
It also prevents the entrainment of drywall dust into combustion air,
which can cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is maintained between
55°F (13°C) and 80°F (27°C), with no evening setback or shutdown.
The use of the furnace while the structure is under construction is
deemed to be intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on the furnace
rating plate, and the gas input rate has been set to the nameplate value.
The filters used to clean the circulating air during the construction
process must be either changed or thoroughly cleaned prior to
occupancy.
– The furnace, ductwork and filters are cleaned as necessary to remove
drywall dust and construction debris from all HVAC system
components after construction is completed.
Verify proper furnace operating conditions including ignition, gas
input rate, air temperature rise, and venting according to these
installation instructions.
WARNING
!
CARBON MONOXIDE POISONING / COMPONENT
DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death
and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue
gas, which could leak into the living space. Air for combustion must not
be contaminated by halogen compounds, which include fluoride,
chloride, bromide, and iodide. These elements can corrode heat
exchangers and shorten furnace life. Air contaminants are found in
aerosol sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products. Do not install furnace in a
corrosive or contaminated atmosphere. Make sure all combustion and
circulating air requirements are met, in addition to all local codes and
ordinances.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
A02097
Fig. 6 – Multipoise Orientations
NOTE: For high-altitude installations, the high-altitude conversion kit
MUST be installed at or above 5500 ft. (1676 M) above sea level. Obtain
high-altitude conversion kit from your area authorized distributor.
This furnace must:
be installed so the electrical components are protected from water.
not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
be located close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
be provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown on the
furnace clearance to combustible construction label.
The following types of furnace installations may require OUTDOOR
AIR for combustion due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Laundry rooms
Hobby or craft rooms, and
Chemical storage areas
If air is exposed to the following substances, it should not be used for
combustion air, and outdoor air may be required for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All fuel-burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative pressure
in the equipment room or space. A positive seal must be made between
the furnace cabinet and the return-air duct to prevent pulling air from the
burner area and from draft safeguard opening.
AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be
provided in accordance with:
U.S. Installations: Section 9.3 of the NFPA 54/ANSI Z223.1, Air
for Combustion and Ventilation and applicable provisions of the
local building codes.
The requirements for combustion and ventilation air depend upon
whether or not the furnace is located in a space having a volume of at
least 50 cubic feet per 1,000 Btuh input rating for all gas appliances
installed in the space.
Spaces having less than 50 cubic feet per 1,000 Btuh require the
OUTDOOR COMBUSTION AIR METHOD.
Spaces having at least 50 cubic feet per 1,000 Btuh may use the
INDOOR COMBUSTION AIR, STANDARD or KNOWN AIR
INFILTRATION METHOD.
Minimum dimensions of 3-in. (76 mm).
NOTE: Use any of the following combinations of openings:
A & B C & D D & E F & G
A03174
Fig. 7 – Air for Combustion, Ventilation, and Dilution for Outdoors
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion,
ventilation, and dilution of flue gases using permanent horizontal or
vertical duct(s) or opening(s) directly communicating with the
outdoors or spaces that freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS,
one inlet and one outlet combustion and ventilation air opening, to
the outdoors.
a. One opening MUST commence within 12 in. (300 mm) of the
ceiling and the second opening MUST commence within 12 in.
(300 mm) of the floor.
CAUTION
!
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen compounds,
which include fluoride, chloride, bromide, and iodide. These elements
can corrode heat exchangers and shorten furnace life. Air contaminants
are found in aerosol sprays, detergents, bleaches, cleaning solvents,
salts, air fresheners, and other household products.
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers,
attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE
CONDITION at the furnace. Make-up air MUST be provided for the
ventilation devices, in addition to that required by the furnace. Refer to
the Carbon Monoxide Poisoning Hazard warning in the venting section
of these instructions to determine if an adequate amount of make-up air
is available.
1 SQ IN.
PER
4000
BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH*
CIRCULATING
AIR DUCTS
VENT
THROUGH
ROOF
D
B
A
C
E
1 SQ IN.
PER 4000
BTUH*
DUCT
TO
OUTDOORS
CIRCULATING AIR DUCTS
1 SQ IN.
PER 2000
BTUH*
1 SQ IN.
PER 2000
BTUH*
DUCTS
TO
OUTDOORS
12 MAX
12 MAX
12 MAX
12
MAX
12
MAX
OUTDOORS
1 SQ IN.
PER
4000
BTUH*
F
G
CLEARANCE IN FRONT
OF COMBUSTION AIR
OPENINGS SHALL BE
AT LEAST 3 IN.
(305mm)
(305mm)
(305mm)
(305mm)
(305mm)
(76mm)
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
b. Size openings and ducts per Fig. 7 and Table 1.
c. TWO HORIZONTAL DUCTS require 1 sq. in. (645 sq. mm) of
free area per 2,000 Btuh (1,100 mm
2
/kW) of combined input for
all gas appliances in the space per Fig. 7 and Table 1.
d. TWO OPENINGS OR VERTICAL DUCTS require 1 sq. in.
(645 sq. mm) of free area per 4,000 Btuh (550 mm
2
/kW) for
combined input of all gas appliances in the space per Fig. 7 and
Table 1.
3. ONE OUTDOOR OPENING requires:
a. 1 sq. in. (645 sq. mm) of free area per 3,000 Btuh (734 mm
2
/kW)
for combined input of all gas appliances in the space per Table 1
and
b. Not less than the sum of the areas of all vent connectors in the
space.
.
NP = Not Permitted
The opening shall commence within 12 in. (300 mm) of the ceiling.
Appliances in the space shall have clearances of at least 1 in. (25 mm)
from the sides and back and 6 in. (150 mm) from the front. The opening
shall directly communicate with the outdoors or shall communicate
through a vertical or horizontal duct to the outdoors or spaces (crawl or
attic) that freely communicate with the outdoors.
Indoor Combustion Air
©
NFPA & AGA
Standard and Known-Air-Infiltration Rate Methods
Indoor air is permitted for combustion, ventilation, and dilution, if
the Standard or Known-Air-Infiltration Method is used.
The Standard Method:
Use the Standard Method if:
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of
the maximum input ratings for all gas appliances installed in the
space and
2. The air infiltration rate is not known to be less than 0.40 air changes
per hour (ACH).
Table 1 – Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors
FURNACE
INPUT
(BTUH)
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS
(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)
Free Area of Opening and
Duct
Sq. In. (Sq. mm)
Round Duct Dia.
In. (mm)
Free Area of Opening and
Duct
Sq. In. (Sq. mm)
Round Duct Dia.
In. (mm)
Free Area of Opening and
Duct
Sq. In. (Sq. mm)
Round Duct Dia.
In. (mm)
44,000 22 (14194) 6 (152) 14.7 (9484) 5 (127) 11 (7096) 4 (102)
66,000 33 (21290) 7 (178) 22 (14193) 6 (152) 16.5 (10645) 5 (127)
88,000 44 (28387) 8 (203) 29.3 (18903) 7 (178) 22 (14193) 6 (152)
110,000 55 (35484) 9 (229) 36.7 (23677) 7 (178) 27.5 (17742) 6 (152)
132,000 66 (42580) 10 (254) 44 (28387) 8 (203) 33 (21290) 7 (178)
EXAMPLES: DETERMINING FREE AREA
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) =
35.3 Sq. In. for a Single Duct or Opening
88,000 + 30,000 = (118,000 divided by 2,000) =
59.0 Sq. In. for each of two Horizontal Ducts
Table 2 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
ACH
30 40 50 44 66 88 110 132 154
Space Volume Ft
3
(M
3
)
0.60
1,050
(29.7)
1,400
(39.6)
1,750
(49.5)
1,100
(31.1)
1,650
(46.7)
2,200
(62.2)
2,750
(77.8)
3,300
(93.4)
3,850
(109.0)
0.50
1,260
(35.6)
1,680
(47.5)
2,100
(59.4)
1,320
(37.3)
1,980
(56.0)
2,640
(74.7)
3,300
(93.4)
3,960
(112.1)
4,620
(130.8)
0.40
1,575
(44.5)
2,100
(59.4)
2,625
(74.3)
1,650
(46.7)
2,475
(70.0)
3,300
(93.4)
4,125
(116.8)
4,950
(140.1)
5,775
(163.5)
0.30
2,100
(59.4)
2,800
(79.2)
3,500
(99.1)
2,200
(62.2)
3,300
(93.4)
4,400
(124.5)
5,500
(155.7)
6,600
(186.8)
7,700
(218.0)
0.20
3,150
(89.1)
4,200
(118.9)
5,250
(148.6)
3,300
(93.4)
4,950
(140.1)
6,600
(186.8)
8,250
(233.6)
9,900
(280.3)
11,550
(327.0)
0.10
6,300
(178.3)
8,400
(237.8)
10,500
(297.3)
6,600
(186.8)
9,900
(280.3)
13,200
(373.7)
16,500
(467.2)
19,800
(560.6)
23,100
(654.1)
0.00 NP NP NP NP NP NP NP NP NP
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Many homes require air to be supplied from outdoors for furnace
combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in accordance
with this instruction manual.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
8
Use the Known Air Infiltration Rate Method if the infiltration rate is
known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum
required volume of the space varies with the number of ACH and shall
be determined per Table 2 or Equations 1 and 2. Determine the minimum
required volume for each appliance in the space and add the volumes
together to get the total minimum required volume for the space.
Table 2 - Minimum Space Volumes were determined by using the
following equations from the National Fuel Gas Code ANSI
Z223.1/NFPA 54, 9.3.2.2:
1. For other than fan-assisted appliances, such as a draft
hood-equipped water heater, use the following equation:
A04002
2. For fan-assisted appliances such as this furnace, use the following
equation:
A04003
If the following is applied to either equation:
I
other = combined input of all other than fan-assisted appliances in
Btuh/hr
I
fan = combined input of all fan-assisted appliances in Btuh/hr
ACH = air changes per hour (ACH shall not exceed 0.60.)
* Minimum opening size is 100 sq in. (64516 sq. mm) with minimum dimensions of 3 in.
(76 mm)
† Minimum of 3 in. (76 mm) when type-B1 vent is used.
A03175
Fig. 8 – Air for Combustion, Ventilation, and Dilution from Indoors
Then the following requirements apply to both the Standard Method
and to the Known Air Infiltration Rate Method:
1. Adjoining rooms can be considered part of a space if:
a. There are no closeable doors between rooms.
b. Combining spaces on same floor level. Each opening shall have
free area of at least 1 in.
2
/1,000 Btuh (2,000 mm
2
/kW) of the
total input rating of all gas appliances in the space, but not less
than 100 in.
2
(0.06 m2). One opening shall commence within 12
in. (300 mm) of the ceiling and the second opening shall
commence within 12 in. (300 mm) of the floor. The minimum
dimension of air openings shall be at least 3 in. (80 mm), see
Fig. 8.
c. Combining space on different floor levels. The volumes of
spaces on different floor levels shall be considered as
communicating spaces if connected by one or more permanent
openings in doors or floors having free area of at least 2
in.
2
/1,000 Btuh (4,400 mm
2
/kW) of total input rating of all gas
appliances
2. An attic or crawlspace may be considered a space that freely
communicates with the outdoors provided there are adequate
permanent ventilation openings directly to outdoors having free
area of at least 1-in.
2
/4,000 Btuh of total input rating for all gas
appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration
should be adequate to provide air for combustion, permanent
ventilation and dilution of flue gases. However, in buildings with
unusually tight construction, additional air MUST be provided
using the methods described in the Outdoor Combustion Air
Method section.
4. Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a continuous,
sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include joints
around window and door frames, between sole plates and floors,
between wall-ceiling joints, between wall panels, at penetrations
for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combustion Air
Method below and,
2. Outdoor openings shall be located as required in the Outdoor
Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume divided by
required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the Ratio in a.
above.
c. Minimum size of Outdoor openings shall be the size required in
Outdoor Combustion Air Method above multiplied by reduction
Factor in b. above. The minimum dimension of air openings shall
be not less than 3 in. (80 mm).
INSTALLATION
UPFLOW INSTALLATION
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler
panel, see Fig. 9.
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
A10273
Fig. 9 – Removing Bottom Closure Panel
Volume
Other
=
21ft
3
ACH
I
other
1000 Btu/hr
Volume
Fan
=
15ft
3
ACH
I
fan
1000 Btu/hr
CIRCULATING AIR
DUCTS
6" MIN
(FRONT)
Ü
CIRCULATING AIR DUCTS
VENT THROUGH ROOF
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
12" MAX
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
12" MAX
UNCONFINED
SPACE
INTERIOR
HEATED
SPACE
CLEARANCE IN FRONT OF COMBUSTION AIR
O PE NI N GS S HA LL BE AT LEAST 3 IN.
(305mm)
(152mm)
(305mm)
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. This panel MUST be in place when only side return
air is used.
NOTE: Side return-air openings can be used in UPFLOW and most
HORIZONTAL configurations. Do not use side return-air openings in
DOWNFLOW configuration.
DOWNFLOW INSTALLATION
NOTE: For downflow applications, this furnace is approved for use on
combustible flooring when any one of the following accessories are
used:
Special Base, KGASB
Cased Coil Assembly Part No. CNPV, CNRV, CAP, or CAR
Coil Box Part No. KCAKC
1. Determine application being installed from Table 3.
2. Construct hole in floor, see Table 3 and Fig. 10.
3. Construct plenum to dimensions specified, see Table 3 and Fig. 10.
4. If downflow subbase, KGASB is used, install, see Fig. 11. If Coil
Assembly Part No. CPVP, CAPMP or CNPVP Coil Box Part No.
KCAKC is used, install, see Fig. 12.
NOTE: It is recommended that the perforated supply-air duct flanges be
completely folded over or removed from furnace when installing the
furnace on a factory-supplied cased coil or coil box. To remove the
supply-air duct flange, use wide duct pliers or hand seamers to bend
flange back and forth until it breaks off. Be careful of sharp edges. Refer
to Duct Flanges (Fig. 17) in the “Air Ducts” section.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler
panel, Fig. 9.
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
A96283
Fig. 10 – Floor and Plenum Opening Dimensions
A96285
Fig. 11 – Furnace, Plenum, and Subbase Installed on a Combustible
Floor
A08556
Fig. 12 – Furnace, Plenum, and Coil Assembly or Coil Box Installed
on a Combustible Floor
HORIZONTAL INSTALLATION
The furnace can be installed horizontally in an attic or crawlspace on
either the left-hand (LH) or right-hand (RH) side. The furnace can be
hung from floor joists, rafters or trusses or installed on a
non-combustible platform, blocks, bricks or pad.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle
iron or metal plumber’s strap as shown, see Fig. 14 and Fig. 15. Secure
angle iron to bottom of furnace as shown. Heavy-gauge sheet metal
straps (plumber’s straps) may be used to suspend the furnace from each
bottom corner. To prevent screws from pulling out, use 2 #8 x in. screws
into the side and 2 #8 x in. screws in the bottom of the furnace casing for
each strap, see Fig. 14 and Fig. 15.
If the screws are attached to ONLY the furnace sides and not the bottom,
the straps must be vertical against the furnace sides and not pull away
from the furnace sides, so that the strap attachment screws are not in
tension (are loaded in shear) for reliable support.
Platform Furnace Support
Construct working platform at location where all required furnace
clearances are met, see Fig. 2 and Fig. 13. For furnaces with 1-in. (25
mm) clearance requirement on side, set furnace on non-combustible
blocks, bricks or angle iron. For crawlspace installations, if the furnace
is not suspended from the floor joists, the ground underneath furnace
must be level and the furnace set in blocks or bricks.
PLENUM
OPENING
C
A
B
D
FLOOR
OPENING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
APPROVED
COIL ASSEMBLY
OR
COIL BOX
FURNACE
SHEET METAL
PLENUM
FLOOR
OPENING
COMBUSTIBLE
FLOORING
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
Roll-Out Protection
Provide a minimum 17-3/4-in. X 22-in. (451 X 559 mm) piece of sheet
metal for flame roll-out protection in front of burner area for furnaces
closer than 12-in. (305 mm) above the combustible deck or suspended
furnaces closer than 12-in. (305 mm) to joists. The sheet metal MUST
extend underneath the furnace casing by 1-in. (25 mm) with the door
removed.
The bottom closure panel on furnaces of widths 17-1/2-in. (445 mm) and
larger may be used for flame roll-out protection when bottom of furnace
is used for return air connection. See Fig. 13 for proper orientation of
roll-out shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler
panel, see Fig. 9.
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
A10164
Fig. 13 – Typical Attic Installation
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. This panel MUST be in place when side return air
inlet(s) are used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections,
see Fig. 20.
Table 3 – Opening Dimensions - In. (mm)
FURNACE
CASING
WIDTH
IN. (mm)
APPLICATION
PLENUM OPENING FLOOR OPENING
A B C D
14–3/16
(360)
Upflow Applications on Combustible or Noncombustible
Flooring (subbase not required)
12-11/16
(322)
21-5/8
(549)
13-5/16
(338)
22-1/4
(565)
Downflow Applications on Noncombustible Flooring
(subbase not required)
12-9/16
(319)
19
(483)
13-3/16
(335)
19-5/8
(498)
Downflow applications on Combustible Flooring
(subbase required)
11-13/16
(284)
19
(483)
13-7/16
(341)
20-5/8
(600)
Downflow Applications on Combustible Flooring with coil assembly or coil
box (subbase not required)
12-5/16
(319)
19
(483)
13-5/16
(338)
20
(508)
17–1/2
(445)
Upflow Applications on Combustible or Noncombustible
Flooring (subbase not required)
16
(406)
21-5/8
(549)
16-5/8
(422)
22-1/4
(565)
Downflow Applications on Noncombustible Flooring
(subbase not required)
15-7/8
(403)
19
(483)
16-1/2
(419)
19-5/8
(498)
Downflow Applications on Combustible Flooring
(subbase required)
15-1/8
(384)
19
(483)
16-3/4
(425)
20-5/8
(600)
Downflow Applications on Combustible Flooring with coil assembly or coil
box (subbase not required)
15-1/2
(394)
19
(483)
16-1/2
(419)
20
(508)
21
(533)
Upflow Applications on Combustible or Noncombustible
Flooring (subbase not required)
19-1/2
(495)
21-5/8
(549)
20-1/8
(511)
22-1/4
(565)
Downflow Applications on Noncombustible Flooring
(subbase not required)
19-3/8
(492)
19
(483)
20
(508)
19-5/8
(498)
Downflow Applications on Combustible Flooring
(subbase required)
18-5/8
(473)
19
(483)
20-1/4
(514)
20-5/8
(600)
Downflow Applications on Combustible Flooring with coil assembly or coil
box (subbase not required)
19
(483)
19
(483)
20
(508)
20
(508)
24-1/2
(622)
Upflow Applications on Combustible or Noncombustible
Flooring (subbase not required)
23
(584)
21-1/8
(537)
23-5/8
(600)
22-1/4
(565)
Downflow Applications on Noncombustible Flooring
(subbase not required)
22-7/8
(581)
19
(483)
23-1/2
(597)
19-5/8
(498)
Downflow Applications on Combustible Flooring
(subbase required)
22-1/8
(562)
19
(483)
23-3/4
(603)
20-5/8
(600)
Downflow Applications on Combustible Flooring with coil assembly or coil
box (subbase not required)
22-1/2
(572)
19
(483)
23-1/2
(597)
20
(508)
30-IN. (762mm)
MIN WORK AREA
6MIN*
TYPE-B
VENT
17
3
/4
22
SHEET
METAL
SEDIMENT
TRAP
EQUIPMENT MANUAL
SHUT-OFF GAS VALVE
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS,
STUDS, OR FRAMING.
GAS
ENTRY
17
3
/4
(451mm)
OVERALL
4
3
/4
(121mm)
UNDER DOOR
1
(25mm)
UNDER FURNACE
EXTEND OUT 12
(305mm)
FROM FACE OF DOOR
* WHEN USED WITH
SINGLE WALL VENT
CONNECTIONS
UNION
(152mm)
(451mm)
(559mm)
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
11
A10130
Fig. 14 – Horizontal Unit Suspension
A10131
Fig. 15 – Horizontal Suspension with Straps
FILTER ARRANGEMENT
There are no provisions for an internal filter rack in these furnaces. A
field-supplied accessory external filter rack is required.
Refer to the instructions supplied with the external filter rack for
assembly and installation options.
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be used,
see Fig. 16. Install field-supplied, 5/16 X 1-1/2 in. (8 X 38 mm) (max)
corrosion-resistant machine bolts, washers and nuts.
A89014
Fig. 16 – Leveling Legs
NOTE: Bottom closure must be used when leveling legs are used. It
may be necessary to remove and reinstall bottom closure panel to install
leveling legs. To remove bottom closure panel, see Item 1 in Bottom
Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom
corner of furnace, see Fig. 16.
2. For each leg, install nut on bolt and then install bolt with nut in
hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer
if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut
to secure arrangement.
5. Reinstall bottom closure panel if removed.
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream
side of the unit to avoid condensation in the heat exchangers. When
installed parallel with the furnace, dampers or other flow control must
prevent chilled air from entering the furnace. If the dampers are
manually operated, they must be equipped with means to prevent
operation of either unit unless the damper is in the full-heat or full-cool
position.
AIR DUCTS
GENERAL REQUIREMENTS
The duct system should be designed and sized according to accepted
national standards such as those published by: Air Conditioning
Contractors Association (ACCA), Sheet Metal and Air Conditioning
Contractors National Association (SMACNA) or American Society of
Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or
consult The Air Systems Design Guidelines reference tables available
from your local distributor. The duct system should be sized to handle
the required system design CFM at the design external static pressure.
The furnace airflow rates are provided in Table 13-Air Delivery-CFM
(With Filter). When a furnace is installed so that the supply ducts carry
air circulated by the furnace to areas outside the space containing the
WARNING
!
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not install the furnace on its back or hang furnace with control
compartment facing downward. Safety control operation will be
adversely affected. Never connect return-air ducts to the back of the
furnace.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, or death.
Never operate a furnace without a filter or with filter access door
removed.
1
/4" (6mm) THREADED ROD
4 REQ.
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WITH
3 #8 x
3
/4" (19mm) SCREWS
TYPICAL FOR 2 SUPPORTS
1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm)
ANGLE IRON OR UNI-STRUT MAY BE USED
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS
REQ. PER ROD
8" (203mm)
MIN
FOR DOOR REMOVAL
OUTER DOOR
ASSEMBLY
METHOD 2
USE (4) #8 x 3/4 (19 mm) SHEET
METAL SCREWS FOR EACH
STRAP. THE STRAPS
SHOULD BE VERTICAL
AGAINST THE FURNACE
SIDES AND NOT PULL AWAY
FROM THE FURNACE
SIDES.
METHOD 1
FOLD ALL STRAPS UNDER
FURNACE AND SECURE WTH
(4) #8 x 3/4 (19 mm) SHEET METAL SCREWS
(2 SCREWS IN SIDE AND 2 SCREWS
IN BOTTOM).
1
3
/
4
1
3
/
4
1
3/
4
1
3/
4
5/
16
5
/
16
5/
16
5/
16
(44mm)
(8mm)
(44mm)
(8mm)
(8mm)
(8mm)
(44mm)
(44mm)
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
furnace, the return air shall also be handled by duct(s) sealed to the
furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal
supply- and return-duct connections to furnace with code approved tape
or duct sealer.
NOTE: Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to
enhance system performance. When air conditioning is used, a vapor
barrier is recommended.
Maintain a 1-in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36-in. (914 mm) horizontally from
the furnace. See NFPA 90B or local code for further requirements
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow and 10
ft. (3 M) of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used if
constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both acoustical
lining and fibrous ductwork shall comply with NFPA 90B as tested by
UL Standard 181 for Class 1 Rigid air ducts.
SUPPLY AIR CONNECTIONS
For a furnace not equipped with a cooling coil, the outlet duct shall be
provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size that
the heat exchanger can be viewed for possible openings using light
assistance or a probe can be inserted for sampling the air stream. The
cover attachment shall prevent leaks.
Upflow and Horizontal Furnaces
Connect supply-air duct to flanges on furnace supply-air outlet. Bend
flange upward to 90° with wide duct pliers, see Fig. 17. The supply-air
duct must be connected to ONLY the furnace supply-outlet-air duct
flanges or air conditioning coil casing (when used). DO NOT cut main
furnace casing side to attach supply air duct, humidifier, or other
accessories. All accessories MUST be connected to duct external to
furnace main casing.
NOTE: For horizontal applications, the top most flange may be bent
past 9to allow the evaporator coil to hang on the flange temporarily
while the remaining attachment and sealing of the coil are performed.
Downflow Furnaces
Connect supply-air duct to supply-air outlet on furnace. Bend flange
inward past 9with wide duct pliers, see Fig. 17. The supply-air duct
must be connected to ONLY the furnace supply outlet or air conditioning
coil casing (when used). When installed on combustible material,
supply-air duct must be connected to ONLY the factory-approved
accessory subbase, or a factory-approved air conditioning coil casing.
DO NOT cut main furnace casing to attach supply side air duct,
humidifier, or other accessories. All accessories MUST be connected to
duct external to furnace casing.
RETURN AIR CONNECTIONS
A190346
Fig. 17 – Duct Flanges
Downflow Furnaces
The return-air duct must be connected to return-air opening bottom inlet,
see Fig. 1. DO NOT cut into casing sides (left or right). Side opening is
permitted for only upflow and certain horizontal furnaces. Bypass
humidifier connections should be made at ductwork or coil casing sides
exterior to furnace, see Fig. 18.
Upflow and Horizontal Furnaces
The return-air duct must be connected to bottom, sides (left or right), or a
combination of bottom and side(s) of main furnace casing, see Fig. 1.
Bypass humidifier may be attached into unused return air side of the
furnace casing, see Fig. 19 and Fig. 20. Not all horizontal furnace
models are approved for side return air connections, see Fig. 20.
WARNING
!
FIRE HAZARD
A failure to follow this warning could cause personal injury, death
and/or property damage.
Never connect return-air ducts to the back of the furnace. Follow
instructions below.
UPFLOW/
HORIZONTAL
DOWNFLOW
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
13
A02163
Fig. 18 – Downflow Return Air Configurations and Restrictions
A02075
Fig. 19 – Upflow Return Air Configurations and Restrictions
A02162
Fig. 20 – Horizontal Return Air Configurations and Restrictions
DOWNFLOW RETURN AIR CONFIGURATIONS AND RESTRICTIONS
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
14
GAS PIPING
Gas piping must be installed in accordance with national and local
codes. Refer to current edition of NFGC in the U.S.
Installations must be made in accordance with all authorities having
jurisdiction. If possible, the gas supply line should be a separate line
running directly from meter to furnace.
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber
or gas fitter.
2. When flexible connectors are used, the maximum length shall not
exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves are used,
they shall be T-handle valves.
4. The use of copper tubing for gas piping is NOT approved by the
state of Massachusetts.
Refer to Table 4 for recommended gas pipe sizing. Risers must be used
to connect to furnace and to meter. Support all gas piping with
appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft.
(1.8 M). Joint compound (pipe dope) should be applied sparingly and
only to male threads of joints. Pipe dope must be resistant to the action
of propane gas.
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-In. W.C.) or less and a pressure
drop of 0.5-In. W.C. (based on a 0.60 specific gravity gas). Ref: Table 6 and 9.2 NFGC.
An accessible manual equipment shutoff valve MUST be installed
external to furnace casing and within 6 ft. (1.8 M) of furnace. A 1/8-in.
(3 mm) NPT plugged tapping, accessible for test gauge connection,
MUST be installed immediately upstream of gas supply connection to
furnace and downstream of manual equipment shutoff valve.
NOTE: The furnace gas control valve inlet pressure tap connection is
suitable to use as test gauge connection providing test pressure DOES
NOT exceed maximum 0.5 psig (14-In. W.C.) stated on gas control
valve, see Fig. 21.
Some installations require gas entry on right side of furnace (as viewed
in upflow), see Fig. 22.
A04167
Fig. 21 – Redundant Automatic Gas Control Valve
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas
leaks with an open flame. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections. A
fire or explosion may result causing property damage, personal injury
or loss of life.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Use proper length of pipe to avoid stress on gas control manifold and
gas valve.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until gas supply
line is permanently installed to protect the valve from moisture and
debris. Also, install a sediment trap in the gas supply piping at the inlet
to the gas valve.
Table 4 – Maximum Capacity of Pipe
NOMINAL
IRON PIPE
SIZE
IN. (MM)
INTERNAL
DIA.
IN. (MM)
LENGTH OF PIPE - FT (M)
10
(3.0)
20
(6.0)
30
(9.1)
40
(12.1)
50
(15.2)
1/2 (12.7) 0.622(158) 175 120 97 82 73
3/4 (19.0) 0.824 (20.9) 360 250 200 170 151
1 ( 25.4) 1.049 (26.6) 680 465 375 320 285
1-1/4 (31.8) 1.380 (35.0) 1400 950 770 660 580
1-1/2 (38.1) 1.610 (40.9) 2100 1460 1180 990 900
WARNING
!
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal injury, death,
and/or property damage.
If local codes allow the use of a flexible gas appliance connector,
always use a new listed connector. Do not use a connector which has
previously served another gas appliance. Black iron pipe shall be
installed at the furnace gas control valve and extend a minimum of 2-in.
(51 mm) outside the furnace.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to avoid damaging
gas controls and burner misalignment.
REGULATOR COVER SCREW
PLASTIC ADJUST SCREW
LOW STAGE
GAS PRESSURE
REGULATOR ADJUSTMENT
MANIFOLD
PRESSURE TAP
INLET
PRESSURE TAP
ON/OFF SWITCH
REGULATOR SPRING
HIGH STAGE GAS
PRESSURE REGULATOR
ADJUSTMENT
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
15
A08551
Fig. 22 – Burner and Manifold
Install a sediment trap in riser leading to furnace, see Fig. 23. Connect a
capped nipple into lower end of tee. Capped nipple should extend below
level of furnace gas controls. Place a ground joint union between furnace
gas control valve and exterior manual equipment gas shutoff valve.
A 1/8-in. (3 mm) NPT plugged tapping, accessible for test gauge
connection, MUST be installed immediately upstream of gas supply
connection to furnace and downstream of manual equipment shutoff
valve.
A02035
Fig. 23 – Typical Gas Pipe Arrangement
Piping should be pressure and leak tested in accordance with the current
addition of the NFGC in the United States, local, and national plumbing
and gas codes before the furnace has been connected. After all
connections have been made, purge lines and check for leakage at
furnace prior to operating furnace.
If pressure exceeds 0.5 psig (14-In. W.C.), gas supply pipe must be
disconnected from furnace and capped before and during supply pipe
pressure test. If test pressure is equal to or less than 0.5 psig (14-In.
W.C.), turn off electric shutoff switch located on furnace gas control
valve and accessible manual equipment shutoff valve before and during
supply pipe pressure test. After all connections have been made, purge
lines and check for leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and minimum
inlet supply pressures marked on the rating plate with the furnace
burners ON and OFF.
ELECTRICAL CONNECTIONS
See Fig. 24 for field wiring diagram showing typical field 115-v wiring.
Check all factory and field electrical connections for tightness.
Field-supplied wiring shall conform with the limitations of 63°F (33°C)
rise.
2” (51mm)
Street Elbow
UNION
SEDIMENT
TRAP
MANUAL
SHUTOFF
VALVE
(REQUIRED)
GAS
SUPPLY
WARNING
!
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings could result in dangerous operation,
serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury,
death or property damage.
- Before servicing, disconnect all electrical power to furnace.
- When servicing controls, label all wires prior to disconnection.
Reconnect wires correctly.
- Verify proper operation after servicing.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access panel door switch opens 115-v power to control. No
component operation can occur. Do not bypass or close switch with
panel removed.
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
The cabinet MUST have an uninterrupted or unbroken ground
according to NEC NFPA 70 or local codes to minimize personal injury
if an electrical fault should occur. This may consist of electrical wire,
conduit approved for electrical ground or a listed, grounded power cord
(where permitted by local code) when installed in accordance with
existing electrical codes. Refer to the power cord manufacturer’s
ratings for proper wire gauge. Do not use gas piping as an electrical
ground.
CAUTION
!
FURNACE MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent furnace
operation.
Furnace control must be grounded for proper operation or else control
will lock out. Control must remain grounded through green/yellow wire
routed to gas valve and manifold bracket screw.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not connect aluminum wire between disconnect switch and furnace.
Use only copper wire, see Fig. 25.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
A95236
Fig. 24 – Field Wiring Diagram
A190279
Fig. 25 – Field-Supplied External
Electrical Box on Furnace Casing
115-V Wiring
Verify that the voltage, frequency, and phase correspond to that specified
on unit rating plate. Also, check to be sure that service provided by
utility is sufficient to handle load imposed by this equipment. Refer to
rating plate or Table 5 for equipment electrical specifications.
U.S. Installations: Make all electrical connections in accordance with
National Electrical Code (NEC) NFPA 70 and any local codes or
ordinances that might apply.
Use a separate, fused branch electrical circuit with a properly sized fuse
or circuit breaker for this furnace. See Table 5 for wire size and fuse
specifications. A readily accessible means of electrical disconnect must
be located within sight of the furnace.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity
is incorrect, control LED status indicator light will flash rapidly and
furnace will NOT operate.
J-BOX RELOCATION
NOTE: If factory location of J-Box is acceptable, go to next section
(ELECTRICAL CONNECTION to J-Box).
NOTE: On 14-in. (356 mm) wide casing models, the J-Box shall not be
relocated to other side of furnace casing when the vent pipe is routed
within the casing.
1. Remove and save two screws holding J-Box, see Fig. 26.
NOTE: The J-Box cover need not be removed from the J-Box in order
to move the J-Box. Do NOT remove green ground screw inside J-Box,
see Fig. 26.
2. Cut wire tie on loop in furnace wires attached to J-Box.
3. Move J-Box to desired location.
4. Fasten J-Box to casing with the two screws removed in Step 1.
5. Route J-Box wires within furnace away from sharp edges, rotating
parts and hot surfaces.
Table 5 – Electrical Data
FURNACE
SIZE
VOLTS-
HERTZ-
PHASE
OPERATING
VOLTAGE RANGE
*
*. Permissible limits of the voltage range at which the unit operates satisfactorily.
MAX.
UNIT
AMPS
UNIT
AMPACITY
†. Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load
amps.
MAX. WIRE LENGTH
- FT (M)
‡. Length shown is as measured 1 way along wire path between furnace and service panel for maximum 2 percent voltage drop.
MAX. FUSE OR CKT
BKR AMPS
**
**. Time-delay type is recommended.
MIN. WIRE
GAUGE
Max. Min.
36045C17 115-60-1 127 104 9.0 12.0 30 (9.4) 15 14
36070C14 115-60-1 127 104 9.0 12.0 30 (9.4) 15 14
48070C17 115-60-1 127 104 9.0 13.0 28 (8.7) 15 14
60070C21
115-60-1 127 104 14.1 18.4 31 (9.5) 20 12
48090C17
115-60-1 127 104 9.6 12.63 29 (9.0) 15 14
60090C21
115-60-1 127 104 14.7 19.0 30 (9.2) 20 12
60110C21 115-60-1 127 104 15.0 19.3 29 (9.1) 20 12
66135C24
115-60-1 127 104 15.0 19.3 29 (9.1) 20 12
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
JUNCTION
BOX
CONTROL
BOX
24-VOLT
TERMINAL
BLOCK
THREE-WIRE
HEATING-
ONLY
FIVE
WIRE
NOTE 2
NOTE 1
1-STAGE
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
CONDENSING
UNIT
FURNACE
COM
R
WCY RG
GND
GND
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
Connect Y/Y2-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
208/230- O
R
460-VOLT
THREE
PHASE
208/230-
VOLT
SINGLE
PHASE
W
HT
BLK
WHT
BLK
W/W1
W2
Y/Y2
G
NOTES: 1.
2.
3.
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
17
A10291
Fig. 26 – Relocating J-Box
Electrical Connection to J-Box
Electrical Box on Furnace Casing Side
A190278
Fig. 27 – Field-Supplied Electrical Box on Furnace Casing
1. Select and remove a hole knockout in the casing where the
electrical box is to be installed.
NOTE: Check that duct on side of furnace will not interfere with
installed electrical box.
2. Remove the desired electrical box hole knockout and position the
hole in the electrical box over the hole in the furnace casing.
3. Fasten the electrical box to casing by driving two field-supplied
screws from inside electrical box into casing steel.
4. Remove and save two screws holding J-Box, see Fig. 26.
5. Pull furnace power wires out of 1/2-in. (12 mm) diameter hole in
J-Box. Do not loosen wires from strain-relief wire-tie on outside of
J-Box.
6. Route furnace power wires through holes in casing and electrical
box and into electrical box.
7. Pull field power wires into electrical box.
8. Remove cover from furnace J-Box.
9. Route field ground wire through holes in electrical box and casing,
and into furnace J-Box.
10. Reattach furnace J-Box to furnace casing with screws removed in
Step 4.
11. Secure field ground wire to J-Box green ground screw.
12. Complete electrical box wiring and installation. Connect line
voltage leads, see Fig. 27. Use best practices (NEC in U.S. for wire
bushings, strain relief, etc.
13. Reinstall cover to J-Box. Do not pinch wires between cover and
bracket.
Power Cord Installation in Furnace J-Box
NOTE: Power cords must be able to handle the electrical requirements
listed in Table 5. Refer to power cord manufacturer’s listings.
1. Remove cover from J-Box.
2. Route listed power cord through 7/8-in. (22 mm) diameter hole in
J-Box.
3. Secure power cord to J-Box bracket with a strain relief bushing or a
connector approved for the type of cord used.
4. Secure field ground wire to green ground screw on J-Box bracket.
5. Connect line voltage leads, see Fig. 24.
6. Reinstall cover to J-Box. Do not pinch wires between cover and
bracket.
BX Cable Installation in Furnace J-Box
1. Remove cover from J-Box.
2. Route BX cable into 7/8-in. (22 mm) diameter hole in J-Box.
3. Secure BX cable to J-Box bracket with connectors approved for the
type of cable used.
4. Secure field ground wire to green ground screw on J-Box bracket.
5. Connect line voltage leads, see Fig. 24.
6. Reinstall cover to J-Box. Do not pinch wires between cover and
bracket.
24-V Wiring
Make field 24-v connections at the 24-v terminal strip, see Fig. 24 -
Fig. 35. Connect terminal Y/Y2 as shown in Fig. 28 - Fig. 34 for proper
cooling operation. Use only AWG No. 18, color-coded, copper
thermostat wire.
The 24-v circuit contains an automotive-type, 3-amp. fuse located on the
control. Any direct shorts during installation, service, or maintenance
could cause this fuse to blow. If fuse replacement is required, use ONLY
a 3-amp. fuse of identical size.
ACCESSORIES
1. Electronic Air Cleaner (EAC)
Connect an accessory Electronic Air Cleaner (if used) using 1/4-in
female quick connect terminals to the two male 1/4-in
quick-connect terminals on the control board marked EAC-1 and
EAC-2. The terminals are rated for 115VAC, 1.0 amps maximum
and are energized during blower motor operation, see Fig. 35.
2. Humidifier (HUM)
Connect an accessory 24 VAC, 0.5 amp. maximum humidifier
(if used) to the 1/4-in male quick-connect HUM terminal and
COM-24V screw terminal on the control board thermostat strip.
The HUM terminal is energized when blower is energized in
heating, see Fig. 35.
NOTE: DO NOT connect furnace control HUM terminal to HUM
(humidifier) terminal on Thermostat, Zone Controller or similar device.
See Thermostat, Zone Controller, thermostat, or controller
manufacturer’s instructions for proper connection.
WARNING
!
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
If field-supplied manual disconnect switch is to be mounted on furnace
casing side, select a location where a drill or fastener cannot damage
electrical or gas components.
FactoryFactory
InstalledInstalled
AlternateAlternate
LocationLocation
GROUND
NEUTRAL
INE VOLTAGE
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
18
A190166
Fig. 28 – Variable Furnace with Single-Speed Air Conditioner
A190170
Fig. 29 – Dual-Fuel Thermostat with Variable Furnace
and Single-Speed Heat Pump
A190167
Fig. 30 – Variable Furnace with Two-Speed Air Conditioner
A190171
Fig. 31 – Dual-Fuel Thermostat with Variable Furnace and
Two-Speed Heat Pump
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
19
A190168
Fig. 32 – Variable Furnace with Single-Speed Heat Pump
(Dual Fuel)
A190169
Fig. 33 – Variable Furnace with Two-Speed Heat Pump
(Dual Fuel)
A190172
Two-Stage Thermostat with Variable Furnace
and Two-Speed Air Conditioner
A190173
Fig. 34 – Single-Stage Thermostat with Variable Furnace and
Two-Speed Air Conditioner
NOTES FOR FIGURE 28 - FIGURE 35
1. Heat pump MUST have a high pressure switch for dual fuel
applications.
2. Refer to outdoor equipment Installation Instructions for additional
information and setup procedure.
3. If the heat pump date code is 1501E or earlier, select the “ZONE”
position on the two-speed heat pump control.
Heat pumps having date codes 1601E and later do not have or
require a “ZONE” selection.
4. Outdoor Air Temperature Sensor must be attached in all dual fuel
applications.
5. Dip switch No. 1 on Thermidistat should be set in OFF position for
air conditioner installations. This is factory default.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
20
6. Dip switch No. 1 on Thermidistat should be set in ON position for
heat pump installations.
7. Dip switch No. 2 on Thermidistat should be set in OFF position for
single-speed compressor operation.
This is factory default.
8. Dip switch No. 2 on Thermidistat should be set in ON position for
two-speed compressor operation.
9. Configuration Option No. 10 “Dual Fuel Selection” must be turned
ON in all dual fuel applications.
10. NO connection should be made to the furnace HUM terminal when
using a Thermidistat.
11. Optional connection: If wire is connected, dip switch SW1-2 on
furnace control should be set in ON position
to allow Thermidistat/Thermostat to control furnace staging.
12. Optional connection: If wire is connected, ACRDJ jumper on
furnace control should be removed to
allow Thermidistat/Thermostat to control outdoor unit staging.
13. Furnace must control its own high-stage heating operation via
furnace control algorithm.
14. The RVS Sensing terminal L” should not be connected. This is
internally used to sense defrost operation.
15. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE
POINT” option on the two-speed heat pump
control board. This is controlled internally by the
Thermidistat/Dual Fuel Thermostat.
16. Dip switch D on Dual Fuel Thermostat should be set in OFF
position for single-speed compressor operation.
This is factory default.
17. Dip switch D on Dual Fuel Thermostat should be set in ON position
for two-speed compressor operation.
A11617
Fig. 35 – Variable Speed Furnace Control for ECM Blower Motor
VENTING
The furnace shall be connected to a listed factory built chimney or vent,
or a clay-tile lined masonry or concrete chimney. Venting into an unlined
masonry chimney or concrete chimney is prohibited.
When an existing Category I furnace is removed or replaced, the original
venting system, may no longer be sized to properly vent the attached
appliances. An improperly sized Category I venting system could cause
the formation of condensate in the furnace and vent, leakage of
condensate and combustion products, and spillage of combustion
products into the living space.
Vent system or vent connectors may need to be resized. Vent systems or
vent connectors must be sized to approach minimum size as determined
using appropriate table found in the current edition of NFGC.
GENERAL VENTING REQUIREMENTS
Follow all safety codes for proper vent sizing and installation
requirements, including local building codes, the National Fuel Gas
Code NFPA 54/ANSI Z223.1 (NFGC), Parts 12 and 13 in the United
States, the local building codes, and furnace and vent manufacturers’
instructions.
These furnaces are design-certified as Category I furnaces in accordance
with ANSI Z21.47/CSA 2.3 and operate with a non-positive vent static
pressure to minimize the potential for vent gas leakage. Category I
furnaces operate with a flue loss not less than 17 percent to minimize the
potential for condensation in the venting system. These furnaces are
approved for common venting and multistory venting with other fan
assisted or draft hood equipped appliances in accordance with the
NFGC, the local building codes, and furnace and vent manufacturers’
instructions. The following information and warning must be considered
in addition to the requirements defined in the NFGC.
24-V THERMOSTAT
TERMINALS
PL2 HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
115-VAC (L2) NEUTRAL
CONNECTIONS
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
PL1 LOW VOLTAGE MAIN
HARNESS CONNECTOR
TRANSFORMER 24-VAC
CONNECTIONS
3-AMP FUSE
STATUS AND COMM
LED LIGHTS
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
MODEL PLUG
CONNECTOR
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
COMMUNICATION
CONNECTOR
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
OUTDOOR
AIR TEMP
CONNECTOR
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
SW4 SETUP
SWITCHES
SOFTWARE
VERSION
PART NUMBER AND
DATE CODE WWYY
ACRDJ AIR
CONDITIONING
RELAY DISABLE
JUMPER
PL3 ECM BLOWER
HARNESS
CONNECTOR
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do not bypass the draft safeguard switch, as an unsafe condition could
exist which must be corrected.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
21
1. If a vent (common or dedicated) becomes blocked, the furnace will
be shut off by the draft safeguard switch located on the vent elbow.
2. Two-stage furnaces require Type B vent connectors outside the
casing in all configurations. Single wall vent connector may be
used inside the furnace casing with the transition to Type B vent
outside the furnace casing. Size the connector so that the FAN-Min
vent connector capacity is equal to or lower than the low fire rate of
the furnace and the FAN-Max vent connector capacity is equal to or
higher than the furnace high fire rate.
3. Do not vent this Category I furnace into a single wall dedicated or
common vent. The dedicated or common vent is considered to be
the vertical portion of the vent system that terminates outdoors.
4. Vent connectors serving Category I furnaces shall not be connected
into any portion of a mechanical draft system operating under
positive pressure.
5. Do not vent this appliance with any solid fuel burning appliance.
6. Category I furnaces must be vented vertically or nearly vertically
unless equipped with a listed mechanical venter. See SIDEWALL
VENTING section.
7. Do not vent this appliance into an unlined masonry chimney. (Refer
to Chimney Inspection Chart, Fig. 36.
Masonry Chimney Requirement
NOTE: These furnaces are CSA design-certified for use in exterior
tile-lined masonry chimneys with a factory accessory Chimney Adapter
Kit. Refer to the furnace rating plate for correct kit usage. The Chimney
Adapter Kits are for use with ONLY furnaces having a Chimney Adapter
Kit number marked on the furnace rating plate.
If a clay tile-lined masonry chimney is being used and it is exposed to
the outdoors below the roof line, relining might be required. Chimneys
shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel Burning Appliances ANSI/NFPA 211 in the United States and must
be in good condition.
U.S.A. Refer to Sections 13.1.8 and 13.2.20 of the NFPA 54/ANSI
Z223.1 or the authority having jurisdiction to determine whether relining
is required. If relining is required, use a properly sized listed metal liner,
Type-B vent, or a listed alternative venting design.
NOTE: See the NFPA 54/ANSI Z223.1 13.1.9 and 13.2.20 regarding
alternative venting design and the exception, which cover installations
such as our Chimney Adapter Kits which are listed for use with these
furnaces. See Product Data Sheet for accessory listing.
A10133
Fig. 36 – Chimney Inspection Chart
The Chimney Adapter Kit is a listed alternative venting system for these
furnaces. See the kit instructions for complete details.
This furnace is permitted to be vented into a clay tile-lined masonry
chimney that is exposed to the outdoors below the roof line, provided:
1. Vent connector is Type-B double-wall, and
2. This furnace is common vented with at least 1 draft hood equipped
appliance, and
3. The combined appliance input rating is less than the maximum
capacity given in Table 6, and
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected
to the venting system being placed into operation could result in carbon
monoxide poisoning or death.
The following steps shall be followed for each appliance connected to
the venting system being placed into operation, while all other
appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as
required in the National Fuel Gas Code, NFPA 54/ANSI Z223.1
and these instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies, which could
cause an unsafe condition.
3. As far as practical, close all building doors and windows and all
doors between the space in which the appliance(s) connected to
the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the
venting system. Turn on any exhaust fans, such as range hoods and
bathroom exhausts, so they are operating at maximum speed. Do
not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being
inspected into operation. Adjust the thermostat so appliance is
operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft
hood relief opening after 5 minutes of main burner operation. Use
the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the
venting system must be corrected in accordance with the National
Fuel Gas Code, NFPA 54/ANSI Z223.1.
9. After it has been determined that each appliance connected to the
venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace dampers and any
other gas-fired burning appliance to their previous conditions of
use.
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances
Consult
Par t C of
chimney adapter venting
instructions for
application
suitability
Is chimney
lined with properly
sized, listed liner or
Type-B vent?
Is chimney
to be dedicated to
a single
furnace?
Chimney
exposed to
outdoors below
roof line?
Repair
liner or top seal
or reline chimney as
necessary.
Mortar
or tile
debris?
Clay
tile misalignment,
missing sections,
gaps?
Debris
in cleanout?
Mortar, tile, metal vent,
fuel oil residue?
Is
liner and top
seal in good
condition?
Is chimney
property lined with
clay tile liner?
Crown
condition:
Missing mortar
or brick?
Rebuild
crown.
Ye s
Ye s
No
No
No
Reline
Ye s
Repair
Ye s
Ye s
Ye s
No
No
Remove mortar
and tile debris
Remove metal vent
or liner.
No
No
No
No
Ye s
Ye s
Suitable
Suitable
Not Suitable
Line chimney with property
sized, listed flexible metal
liner or Type-B vent per
NFGC
Vent
Sizing Tables and liner or
vent manufacturer’s
Installation instructions.
Install chimney
adapter per
instructions.
Chimney is
acceptable for use.
Install chimney
adapter per
instructions.
Consult
Par t B of
chimney adapter venting
instructions for
application
suitability.
Ye s
Not Suitable
Condensate
drainage at bottom
of chimney?
Ye s
No
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
22
4. The input rating of each space heating appliance is greater than the
minimum input rating given in Table 6 for the local 99% Winter
Design Temperature. Chimneys having internal areas greater than
38 sq. in. (24516 sq. mm) require furnace input ratings greater than
the input ratings of these furnaces. See footnote at bottom of
Table 6, and
5. The authority having jurisdiction approves.
If all of these conditions cannot be met, an alternative venting design
shall be used, such as the listed chimney adapter kit with a furnace listed
for use with the kit, a listed chimney-lining system, or a Type-B common
vent.
Inspections before the sale and at the time of installation will determine
the acceptability of the chimney or the need for repair and/or (re)lining.
Refer to Fig. 36 to perform a chimney inspection. If the inspection of a
previously used tile-lined chimney:
a. Shows signs of vent gas condensation, the chimney should be
relined in accordance with local codes and the authority having
jurisdiction. The chimney should be relined with a listed metal
liner, Type-B vent, or a listed chimney adapter kit shall be used to
reduce condensation. If a condensate drain is required by local
code, refer to the NFPA 54/ANSI Z223.1, Section 12.10 for
additional information on condensate drains.
b. Indicates the chimney exceeds the maximum permissible size in
the tables, the chimney should be rebuilt or relined to conform to
the requirements of the equipment being installed and the
authority having jurisdiction.
A chimney without a clay tile liner, which is otherwise in good
condition, shall be rebuilt to conform to ANSI/NFPA 211 or be lined
with a UL listed metal liner or UL listed Type-B vent. Relining with a
listed metal liner or Type-B vent is considered to be a vent-in-a-chase.
If a metal liner or Type-B vent is used to line a chimney, no other
appliance shall be vented into the annular space between the chimney
and the metal liner.
EXTERIOR MASONRY CHIMNEY FAN + NAT
INSTALLATIONS WITH TYPE-B DOUBLE-WALL
VENT CONNECTORS
E
NFPA & AGA
Appliance Application Requirements
Appliance operation has a significant impact on the performance of the
venting system. If the appliances are sized, installed, adjusted, and
operated properly, the venting system and/or the appliances should not
suffer from condensation and corrosion. The venting system and all
appliances shall be installed in accordance with applicable listings,
standards, and codes.
The furnace should be sized to provide 100 percent of the design heating
load requirement plus any margin that occurs because of furnace model
size capacity increments. Heating load estimates can be made using
approved methods available from Air Conditioning Contractors of
America (Manual J); American Society of Heating, Refrigerating, and
Air-Conditioning Engineers; or other approved engineering methods.
Excessive oversizing of the furnace could cause the furnace and/or vent
to fail prematurely.
When a metal vent or metal liner is used, the vent must be in good
condition and be installed in accordance with the vent manufacturer’s
instructions.
To prevent condensation in the furnace and vent system, the following
precautions must be observed:
1. The return-air temperature must be at least 60°F db except for brief
periods of time during warm-up from setback at no lower than 55°F
(13°C) db or during initial start-up from a standby condition.
2. Adjust the gas input rate per the installation instructions. Low gas
input rate causes low vent gas temperatures, causing condensation
and corrosion in the furnace and/or venting system. Derating is
permitted only for altitudes above 2000 Ft. (610 M).
3. Adjust the air temperature rise to the midpoint of the rise range or
slightly above. Low air temperature rise can cause low vent gas
temperature and potential for condensation problems.
4. Set the thermostat heat anticipator or cycle rate to reduce short
cycling.
Table 6 – Minimum Allowable Input Rating of
Space-Heating Appliance in Thousands of Btuh per Hour
VENT HEIGHT
FT. (M)
INTERNAL AREA OF CHIMNEY
SQ. IN. (SQ. MM)
12
(7741)
19
(12258)
28
18064)
38
(24516)
Local 99% Winter Design Temperature: 17 to 26 degrees F
*
*. The 99.6% heating (db) temperatures found in the 1997 or 2001 ASHRAE
Fundamentals Handbook, Climatic Design Information chapter, Table 1A
(United States) and 2A (Canada) or the 2005 ASHRAE Fundamentals
handbook, Climatic Design Information chapter, and the CD-ROM included
with the 2005 ASHRAE Fundamentals Handbook.
6 0 55 99 141
8 52 74 111 154
10 NR 90 125 169
15 NR NR 167 212
20 NR NR 212 258
30 NR NR NR 362
Local 99% Winter Design Temperature: 5 to 16 degrees F
*
6 NR 78 121 166
8 NR 94 135 182
10 NR 111 149 198
15 NR NR 193 247
20 NR NR NR 293
30 NR NR NR 377
Local 99% Winter Design Temperature: -10 to 4 degrees F
*
6 NR NR 145 196
8 NR NR 159 213
10 NR NR 175 231
15 NR NR NR 283
20 NR NR NR 333
30 NR NR NR NR
Local 99% Winter Design Temperature: -11 degrees F or
lower
Not recommended for any vent configuration.
Table 7 – Combined Appliance Maximum Input Rating
in Thousands of Btuh per Hour
VENT HEIGHT
FT (M)
INTERNAL AREA OF CHIMNEY
SQ. IN. (SQ. MM)
12
(7741)
19
(12258)
28
(18064)
38
(24516)
6 (1.8) 74 119 178 257
8 (2.4) 80 130 193 279
10 (3.0) 84 138 207 299
15 (4.5) NR 152 233 334
20 (6.0) NR NR 250 368
30 (9.1) NR NR NR 404
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
23
Air for combustion must not be contaminated by halogen compounds
which include chlorides, fluorides, bromides, and iodides. These
compounds are found in many common home products such as
detergent, paint, glue, aerosol spray, bleach, cleaning solvent, salt, and
air freshener, and can cause corrosion of furnaces and vents. Avoid using
such products in the combustion-air supply. Furnace use during
construction of the building could cause the furnace to be exposed to
halogen compounds, causing premature failure of the furnace or venting
system due to corrosion.
Vent dampers on any appliance connected to the common vent can cause
condensation and corrosion in the venting system. Do not use vent
dampers on appliances common vented with this furnace.
Additional Venting Requirements
A 4-in. (102 mm) round vent elbow is supplied with the furnace. A 5-in.
(127 mm) or 6- in. (152 mm) vent connector may be required for some
model furnaces. A field-supplied 4-in. (102 mm) to 5-in. (127 mm) or
4-in. (102 mm) to 6-in. (152 mm) sheet metal increaser fitting is required
when 5-in. (127 mm) or 6-in. (152 mm) vent connector is used. Refer to
Table 8 to determine the minimum vertical vent height for various
furnace and vent orientations. See Fig. 37 - Fig. 49 Venting Orientation
for approved vent configurations.
NOTE: Vent connector length for connector sizing starts at furnace vent
elbow. The 4-in. (102 mm) vent elbow is shipped for upflow
configuration and may be rotated for other positions. Remove the three
screws that secure vent elbow to furnace, rotate furnace vent elbow to
position desired, reinstall screws. The factory-supplied vent elbow does
NOT count as part of the number of vent connector elbows.
The vent connector can exit the furnace through one of five locations on
the casing.
1. Attach the single wall vent connector to the furnace vent elbow, and
fasten the vent connector to the vent elbow with at least two
field-supplied, corrosion-resistant, sheet metal screws located 180°
apart.
NOTE: An accessory flue extension is available to extend from the
furnace elbow to outside the furnace casing. SeeProduct Data Sheet for
accessory listing. If flue extension is used, fasten the flue extension to
the vent elbow with at least two field-supplied, corrosion-resistant, sheet
metal screws located 180° apart. Fasten the vent connector to the flue
extension with at least two field-supplied, corrosion resistant sheet metal
screws located 180° apart.
2. Vent the furnace with the appropriate connector, see
Fig. 37 - Fig. 49.)
3. Determine the correct location of the knockout to be removed.
4. Use a hammer and screwdriver to strike a sharp blow between the
tie points and work the slug back and forth until the slug breaks
free.
An accessory Vent Guard Kit is REQUIRED for downflow applications
for use where the vent exits through the lower portion of the furnace
casing. Refer to the Vent Guard Kit Instructions for complete details. See
Product Data Sheet for accessory listing.
The horizontal portion of the venting system shall slope upwards not less
than 1/4-in. per linear ft. (21 mm/m) from the furnace to the vent and
shall be rigidly supported every 5 ft. (1.5 M) or less with metal hangers
or straps to ensure there is no movement after installation.
Sidewall Venting
This furnace is not approved for direct sidewall horizontal venting.
Per section 12.4.3 of the NFPA 54/ANSI Z223.1, any listed mechanical
venter may be used, when approved by the authority having jurisdiction.
Select the listed mechanical venter to match the Btuh input of the
furnace being vented. Follow all manufacturer’s installation
requirements for venting and termination included with the listed
mechanical venter.
Caution!! For the following furnace and vent orientations, use the minimum vertical heights as specified in Table 8.
For all other orientations, follow exclusively the National Fuel Gas Code.
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.
CAUTION
!
BURN HAZARD
Failure to follow this caution may result in personal injury.
Hot vent pipe is within reach of small children when installed in
downflow position.
See the following instruction.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts, and servicing furnaces.
Table 8 – Recommended Minimum Vent Height Per Furnace and Vent Orientation
FURNACE
ORIENTATION
VENT ORIENTATION
FURNACE INPUT
(BTUH/HR)
MIN. VENT
DIAMETER
IN. (mm)
*
*. 4-in. (102 mm) inside casing or vent guard
MIN. VERTICAL VENT
HEIGHT
FT. (M)
†. Including 4 in. (102 mm) vent section(s)
Downflow
Vent elbow left, then up
Fig. 42
132,000 & 110,000 5 (127) 12 (3.6)
Horizontal Left
Vent elbow right, then up
Fig. 45
132,000 5 (127) 7 (2.1)
Horizontal Left
Vent Elbow up
Fig. 46
132,000 5 (127) 7 (2.1)
Downflow
Vent elbow up then left
Fig. 38
110,000 5 (127) 10 (3.0)
Downflow
Vent elbow up, then right
Fig. 43
110,000 5 (127) 10 (3.0)
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
A03208
Fig. 37 – Upflow Application - Vent Elbow Up
A03210
Fig. 38 – Downflow Application - Vent Elbow Up then Left
A03209
Fig. 39 – Upflow Application - Vent Elbow Right
A03211
Fig. 40 – Downflow Application - Vent Elbow Up
A03213
Fig. 41 – Horizontal Left Application - Vent Elbow Left
A03207
Fig. 42 – Downflow Application - Vent Elbow Left then Up
SEE NOTES: 1,2,4,7,8,9
on the page following
these figures
SEE NOTES:1,2,3,4,5,7,8,9
on the page following
these figures
SEE NOTES: 1,2,3,4,7,8,9
on the pages following
these figures
SEE NOTES: 1,2,4,5,7,8,9
on the page following
these figures
SEE NOTES: 1,2,4,7,8,9 on the page
following these figures
SEE NOTES: 1,2,4,5,6,7,8,9
on the page following these figures
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
25
A03212
Fig. 43 – Downflow Application - Vent Elbow Up then Right
A03218
Fig. 44 – Horizontal Right Application-Vent Elbow Right
A03214
Fig. 45 – Horizontal Left Application - Vent Elbow Right then Up
A03215
Fig. 46 – Horizontal Left Application - Vent Elbow Up
A03216
Fig. 47 – Horizontal Left Application - Vent Elbow Right
A02068
Fig. 48 – Horizontal Right Application-Vent Elbow Left
A03219
Fig. 49 – Horizontal Right Application - Vent Elbow Left then Up
SEE NOTES:1,2,3,4,5,7,8,9
on the page following
these figures.
SEE NOTES: 1,2,4,7,8,9 on the page
following these figures
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
SEE NOTES: 1,2,4,5,7,8,9
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
Venting Notes for Fig. 37 - Fig. 49
1. For common vent, vent connector sizing and vent material: United States use the NFGC.
2. Immediately increase to 5-in. (102 mm) or 6-in. (152 mm) vent connector outside furnace casing when 5-in. (127 mm) vent connector is required,
refer to Note 1 above.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when factory-approved
Downflow Vent Guard Kit is used in the downflow position. See Product Data Sheet for accessory listing.
4. Type-B vent where required, refer to Note 1 above.
5. A 4-in.(102 mm) single-wall (26 ga. min.) vent must be used inside furnace casing and when the factory-approved Downflow Vent Guard Kit is
used external to the furnace. See Product Data Sheet for accessory listing.
6. Accessory Downflow Vent Guard Kit required in downflow installations with lower vent configuration. See Product Data Sheet for accessory
listing.
7. Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit for sizing and complete
application details. See Product Data Sheet for accessory listing.
8. Secure vent connector to furnace elbow with (2) corrosion-resistant sheet metal screws, spaced approximately 180° apart.
9. Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120° apart. Secure Type-B vent
connectors per vent connector manufacturer’s recommendations.
10. The total height of the vent and connector shall be at least seven feet for the 154,000 Btuh gas input rate model when installed in a downflow
application with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward, see Fig. 42.
START-UP, ADJUSTMENT, AND SAFETY
CHECK
GENERAL
1. Maintain 115-v wiring and ground. Improper polarity will result in
LED and no furnace operation.
2. Make thermostat wire connections at the 24-v terminal block on the
furnace control. Failure to make proper connections will result in
improper operation, see Fig. 24 - Fig. 35.
3. Gas supply pressure to the furnace must be greater than 4.5-In.
W.C. (0.16 psig) but not exceed 14-In. W.C. (0.5 psig).
4. Check all manual-reset switches for continuity.
5. Replace blower compartment door. Door must be in place to
operate furnace.
6. Setup switch descriptions The variable speed furnace control has
DIP switches to select thermostat staging, blower off delay timings,
air flow selection and other operational or service related functions,
see Fig. 35, Fig. 52 and Table 14.
START-UP PROCEDURES
1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.
3. To Begin Component Self-Test:
a. Remove Blower Access Door.
b. Disconnect the thermostat R lead from furnace control board.
c. Manually close blower door switch.
d. Turn Setup DIP switch SW1-6 ON, see Fig. 35, Fig. 56 and
Table 14.
NOTE: The furnace control allows all components, except the gas
valve, to be run for short period of time. This feature helps diagnose a
system problem in case of a component failure. Component test feature
will not operate if any thermostat signal is present at the control.
Refer to service label attached to furnace or see Fig. 52.
4. Component test sequence is as follows:
a. Inducer motor starts on high-speed and continues to run until
Step d. of component test sequence.
b. Hot surface igniter is energized for 15 sec., then off.
c. Blower motor operates for 15 sec.
d. Inducer motor goes to low-speed for 10 sec., then stops.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death or
property damage.
This furnace is equipped with manual reset limit switches in the gas
control area. The switches open and shut off power to the gas valve, if a
flame rollout or overheating condition occurs in the gas control area.
DO NOT bypass the switches. Correct problem before resetting the
switches.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts, and servicing furnaces.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas
leaks with an open flame. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections. A
fire or explosion may result causing property damage, personal injury
or loss of life.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115-v power to control. No
component operation can occur unless switch is closed. Caution must
be taken when manually closing this switch for service purposes.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
27
e. After component test is completed, one or more status codes (11,
25 or 41) will flash. See component test section of service label
(Fig. 52) in furnace for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1-6 OFF, then
back ON.
5. Turn setup DIP switch SW1-6 OFF. Reconnect R lead to furnace
control board, release blower door switch and reinstall blower
access door.
6. Operate furnace per instruction on inner door.
7. Verify furnace shut down by lowering thermostat setting below
room temperature.
8. Verify furnace restarts by raising thermostat setting above room
temperature.
ADJUSTMENTS
A93059
Fig. 50 – Orifice Hole
Furnace gas input rate on rating plate is for installations at altitudes up to
2000 Ft. (610 M). Furnace input rate must be within +/-2 percent of
furnace rating plate input. For altitudes above 5500 Ft. (1676 M), a
field-supplied high altitude pressure switch is required. Perform the
following steps:
1. Determine the correct gas input rate.
The input rating for altitudes above 2,000 ft. (610 M) must be
reduced by 4 percent for each 1,000 ft. (305 M) above sea level.
For installations below 2000 Ft. (610 M), refer to the unit rating
plate. For installations above 2000 Ft. (610 M), multiply the input
on the rating plate by the de-rate multiplier in Table 9 for the
correct input rate.
2. Determine the correct orifice and manifold pressure adjustment. All
models in all positions except Low NOx models in downflow and
horizontal positions use Table 15 (22,000 Btuh per burner.) Low
NOx models in downflow or horizontal positions must use Table 16
(21,000 Btuh per burner.) See input listed on rating plate.
a. Obtain average yearly gas heat value (at installed altitude) from
local gas supplier.
b. Obtain average yearly gas specific gravity from local gas
supplier.
c. Find installation altitude in Table 15 or Table 16.
d. Find closest natural gas heat value and specific gravity in
Table 15 or Table 16.
e. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low-and high-heat manifold
pressure settings for proper operation.
f. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
NOTE: If orifice hole appears damaged or it is suspected to have been
redrilled, check orifice hole with a numbered drill bit of correct size.
Never redrill an orifice. A burr-free and squarely aligned orifice hole is
essential for proper flame characteristics.
g. Replace orifice with correct size, if required by Table 15 or
Table 16. Use only factory-supplied orifices. See Example
below.
3. Adjust manifold pressure to obtain low fire input rate, see Fig. 21.
a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve.
c. Connect a water column manometer or similar device to
manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Move setup SW1-2 on furnace control to ON position to lock
furnace in low-heat operation, see Table 14 and Fig. 35.
f. Manually close blower door switch.
g. Jumper R and W/W1 thermostat connections on control to start
furnace, see Fig. 35.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw. This can
result in unregulated manifold pressure and result in excess overfire and
heat exchanger failures.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes,
etc.) can cause excessive burner noise and misdirection of burner
flames. This can result in flame impingement of heat exchangers,
causing failures, see Fig. 50.
BURNER
ORIFICE
EXAMPLE: 0–2000 ft. (0-610 M) altitude
For 22,000 Btuh per burner application use Table 15.
Heating value = 1000 Btuh/cu ft.
Specific gravity = 0.62
Therefore: Orifice No. 43*
Manifold pressure: 3.7-In. W.C. for high-heat
1.6-In. W.C. for low-heat
* Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the
correct size and do not need to be changed to obtain proper input rate.
Table 9 – Altitude Derate Multiplier for U.S.A.
ALTITUDE
FT. (M)
PERCENT
OF DERATE
DERATE MULTIPLIER
FACTOR*
0–2000
(0-610)
0 1.00
2001–3000
(610-914)
8–12 0.90
3001–4000
(914-1219)
12–16 0.86
4001–5000
(1219-1524)
16–20 0.82
5001–6000
1524-1829)
20–24 0.78
6001–7000
(1829-2134)
24–28 0.74
7001–8000
(2134-2438)
28–32 0.70
8001–9000
(2438-2743)
32–36 0.66
9001–10,000
(2743-3048)
36–40 0.62
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
28
h. Remove regulator adjustment cap from low heat gas valve
pressure regulator (see Fig. 21) and turn low-heat adjusting
screw (3/16 or smaller flat-tipped screwdriver) counterclockwise
(out) to decrease input rate or clockwise (in) to increase input
rate.
NOTE: DO NOT set low-heat manifold pressure less than 1.4-In. W.C.
or more than 1.7-In. W.C. for natural gas. If manifold pressure is outside
this range, change main burner orifices.
i. Install low-heat regulator adjustment cap.
j. Move setup switch SW1-2 to off position after completing
low-heat adjustment.
k. Leave manometer or similar device connected and proceed to
Step 4.
4. Adjust manifold pressure to obtain high fire input rate, see Fig. 21.
a. Jumper R to W/W1 and W2 thermostat connections on furnace
control. This keeps furnace locked in high-heat operation.
b. Remove regulator adjustment cap from high-heat gas valve
pressure regulator, see Fig. 21, and turn high heat adjusting screw
(3/16-in. or smaller flat-tipped screwdriver) counterclockwise
(out) to decrease input rate or clockwise (in) to increase input
rate.
NOTE: DO NOT set high-heat manifold pressure less than 3.2-In. W.C.
or more than 3.8 In. W.C. for natural gas. If manifold pressure is outside
this range, change main burner orifices to obtain manifold pressure in
this range.
c. When correct input is obtained, replace caps that conceal gas
valve regulator adjustment screws. Main burner flame should be
clear blue, almost transparent.
d. Remove jumpers R to W/W1 and R to W2.
5. Verify natural gas input rate by clocking meter.
NOTE: Gas valve regulator adjustment caps must be in place for proper
input to be clocked.
a. Turn off all other gas appliances and pilots served by the meter.
b. Move setup switch SW1-2 to ON position. This keeps furnace
locked in low-heat operation.
c. Jumper R to W/W1.
d. Run furnace for 3 minutes in low-heat operation.
e. Measure time (in sec) for gas meter to complete 1 revolution and
note reading. The 2 or 5 cubic feet dial provides a more accurate
measurement of gas flow.
f. Refer to Table 10 for cubic ft. of gas per hr.
g. Multiply gas rate cu ft./hr by heating value (Btuh/cu ft.) to obtain
input. If clocked rate does not match required input from Step 1,
increase manifold pressure to increase input or decrease manifold
pressure to decrease input. Repeat steps d through g until correct
low-heat input is achieved. Re-install low heat regulator seal cap
on gas valve.
h. Move setup switch SW1-2 to OFF position and jumper R to
W/W1, and W2. This keeps furnace locked in high-heat
operation. Repeat items d through g for high-heat operation.
6. Set Temperature Rise.
NOTE: Blower access door must be installed when taking temperature
rise reading. Leaving blower access door off will result in incorrect
temperature measurements.
When setup switch SW1-4 is ON, operation will be near the high end of
the rise range for improved comfort.
Furnace must operate within ranges of temperature rise specified on the
furnace rating plate. Determine air temperature rise as follows:
a. Place thermometers in return and supply ducts as near furnace as
possible. Be sure thermometers do not see heat exchanger so that
radiant heat does not affect readings. This practice is particularly
important with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine air
temperature rise.
NOTE: Temperature rise can be determined for low-heat operation by
placing setup switch SW1-2 on furnace control in ON position and
jumping R to W/W1. For high-heat operation, place setup switch SW1-2
in OFF position and jumper R to W1 and R-W2 on furnace control. DO
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in shorten furnace life.
Set air temperature rise within limits specified on the rating plate to
prevent reduced life of furnace components. Operation is within a few
degrees of the mid-point of rise range when setup switch SW1-4 is
OFF.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in overheating the heat
exchangers or condensing flue gases in heat exchanger areas not
designed for condensate.
Temperature rise must be within limits specified on unit rating plate.
Operation is within a few degrees of midpoint of rise range when setup
switch SW1-4 is OFF.
Table 10 – Gas Rate (CU ft./hr)
SEC.
FOR 1 REV.
SIZE OF TEST DIAL
SEC. FOR
1 REV.
SIZE OF TEST DIAL
1 Cu
Ft.
2 Cu
Ft.
5 Cu
Ft.
1 Cu
Ft.
2 Cu
Ft.
5 Cu
Ft.
10 360 720 1800 50 72 144 360
11 327 655 1636 51 71 141 355
12 300 600 1500 52 69 138 346
13 277 555 1385 53 68 136 340
14 257 514 1286 54 67 133 333
15 240 480 1200 55 65 131 327
16 225 450 1125 56 64 129 321
17 212 424 1059 57 63 126 316
18 200 400 1000 58 62 124 310
19 189 379 947 59 61 122 305
20 180 360 900 60 60 120 300
21 171 343 857 62 58 116 290
22 164 327 818 64 56 112 281
23 157 313 783 66 54 109 273
24 150 300 750 68 53 106 265
25 144 288 720 70 51 103 257
26 138 277 692 72 50 100 250
27 133 267 667 74 48 97 243
28 129 257 643 76 47 95 237
29 124 248 621 78 46 92 231
30 120 240 600 80 45 90 225
31 116 232 581 82 44 88 220
32 113 225 563 84 43 86 214
33 109 218 545 86 42 84 209
34 106 212 529 88 41 82 205
35 103 206 514 90 40 80 200
36 100 200 500 92 39 78 196
37 97 195 486 94 38 76 192
38 95 189 474 96 38 75 188
39 92 185 462 98 37 74 184
40 90 180 450 100 36 72 180
41 88 176 439 102 35 71 178
42 86 172 429 104 35 69 173
43 84 167 419 106 34 68 170
44 82 164 409 108 33 67 167
45 80 160 400 110 33 65 164
46 78 157 391 112 32 64 161
47 76 153 383 116 31 62 155
48 75 150 375 120 30 60 150
49 73 147 367
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
29
NOT forget to return setup switch to OFF position and remove jumper
upon completion of testing.
c. This furnace is capable of automatically providing proper airflow
to maintain the temperature rise within the range specified on
furnace rating plate. If temperature rise is outside this range,
proceed as follows:
(1.) Check gas input for low- and high-heat operation.
(2.) Check derate for altitude if applicable.
(3.) Check all return and supply ducts for excessive restrictions
causing static pressure greater than 0.5-In. W.C.
(4.) Ensure setup switch SW1-4 (Comfort/Efficiency) is in
OFF=Efficiency position when a bypass humidifier is used,
see Fig. 35 for switch location.)
(5.) Make sure proper model plug is installed.
d. Remove thermostat jumpers and release blower access door
switch.
e. Repeat Steps a through c as required to adjust for high heat
temperature rise.
f. When correct high heat input rate and temperature rise is
achieved, turn gas valve ON/OFF switch to OFF.
g. Release blower access door switch.
h. Remove manometer or similar device from gas valve.
i. Re-install manifold pressure tap plug in gas valve, see Fig. 21.
j. Remove thermostat jumper wire from furnace control board.
k. Turn gas valve ON/OFF switch to ON.
l. Proceed to Step 7, Set Blower Off Delay” before installing
blower access door.
7. Set Blower Off Delay
a. Remove blower access door if installed.
b. Turn Dip switch SW-7 or SW-8 ON or OFF for desired blower
off delay, see Table 11, Table 14, and Fig. 35 and Fig. 56.
8. Set thermostat heat anticipator.
a. Mechanical thermostat. Set thermostat heat anticipator to match
the amp. draw of the electrical components in the R-W/W1
circuit. Accurate amp. draw readings can be obtained at the wires
normally connected to thermostat subbase terminals, R and W.
The thermostat anticipator should NOT be in the circuit while
measuring current.
(1.) Set SW1-2 switch on furnace control board to ON.
(2.) Remove thermostat from subbase or from wall.
(3.) Connect an amp. meter across the R and W subbase
terminals or R and W wires at wall, see Fig. 51.
(4.) Record amp. draw across terminals when furnace is in low
heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat
instructions and install on subbase or wall.
(6.) Turn SW1-2 switch OFF.
(7.) Install blower access door.
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.
9. Set Airflow for Air Conditioning -Single Stage and High Stage
Cooling
The ECM blower can be adjusted for a range of airflow for Low
Speed or High Speed cooling. See Table 13-Air Delivery - CFM
(With Filter). Depending on the model size, the cooling airflow can
be adjusted from 1.5 to 6 tons based on 350 CFM/ton. Refer to
Table 12.
The cooling airflow is adjusted by turning Setup switches SW2-1,
SW2-2 and SW2-3 either ON or OFF. Select the required airflow,
see Fig. 14. Fig. 14 is based on 350 CFM per ton. For airflow at 400
CFM per ton, turn Setup SW1-5 ON, see Table 11, Table 14,
Fig. 35, and Fig. 56.
A96316
Fig. 51 – Amp. Draw Check with Ammeter
NOTE: 5.5 ton airflow will truncate at 2200 cfm on applicable models.
For a complete explanation of cooling airflow, refer to the section titled
“Sequence of Operation.”
10. Set Airflow For Continuous Fan/Low Speed Cooling Airflow The
ECM blower motor can be adjusted for continuous fan speeds
different than heating or cooling fan speed. See Table 13 - Air
Delivery - CFM (With Filter). Select the required continuous fan
airflow, see Fig. 14.
The continuous fan speed is also the switch setting for low speed
cooling when furnace is used with a 2-speed cooling unit. Adjust
the Continuous Fan CFM to match the airflow required for low
speed cooling. Select the required airflow, see Fig. 53. For airflow
at 400 CFM per ton, turn Setup SW1-5 ON, see Fig. 14. The
airflow selected for low speed cooling will also be the airflow used
for continuous fan.
The continuous fan speed can be further adjusted at the thermostat
using the “Comfort Fan” select function. Changing the continuous
fan speed at the thermostat DOES NOT change the low speed
cooling airflow selected at the control board.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
CAUTION
!
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the
rating plate. Recommended operation is at the mid-point of rise range
or slightly above.
Table 11 – Blower Off Delay Setup Switch
DESIRED HEATING MODE
BLOWER OFF DELAY (SEC.)
SETUP SWITCH
(SW-7 AND -8)
POSITION
SW1-7 SW1-8
90 OFF OFF
120 ON OFF
150 OFF ON
180 ON ON
R Y W G
10 TURNS
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
EXAMPLE:
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
=
0.5 AMPS FOR THERMOSTAT
ANTICIPATOR SETTING
FROM UNIT 24-V
CONTROL TERMINALS
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
30
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the
Start-up procedure section as part of normal operation.
1. Check Main Limit Switch
This control shuts off combustion system and energizes
air-circulating blower motor, if furnace overheats. By using this
method to check limit control, it can be established that limit is
functioning properly and will operate if there is a restricted
return-air supply or motor failure. If limit control does not function
during this test, cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of cardboard or sheet
metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re-light when furnace cools down.
2. Check draft safeguard switch. The purpose of this control is to
cause the safe shutdown of the furnace during certain blocked vent
conditions.
a. Verify vent pipe is cool to the touch.
b. Disconnect power to furnace and remove vent connector from
furnace vent elbow.
c. Restore power to furnace and set room thermostat above room
temperature.
d. After normal start-up, allow furnace to operate for 2 minutes,
then block vent elbow in furnace 80 percent of vent area with a
piece of flat sheet metal.
e. Furnace should cycle off within 2 minutes. If gas does not shut
off within 2 minutes, determine reason draft safeguard switch did
not function properly and correct condition.
NOTE: Should switch remain open longer than 3 minutes, furnace
control board will lockout the furnace for 3 hours. To reset furnace
control board, turn thermostat below room temperature or from HEAT to
OFF and turn 115-v power OFF, then back ON.
f. Remove blockage from furnace vent elbow.
g. Switch will auto-reset when it cools.
h. Re-install vent connector.
3. Check Pressure Switch(es)
This control proves operation of the draft inducer blower.
a. Turn off 115-v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115-v power to furnace.
d. Set thermostat to “call for heat” and wait 1 minute. When
pressure switch is functioning properly, hot surface igniter
should NOT glow and control diagnostic light flashes a status
code 32. If hot surface igniter glows when inducer motor is
disconnected, shut down furnace immediately.
e. Determine reason pressure switch did not function properly and
correct condition.
f. Turn off 115-v power to furnace.
g. Reconnect inducer motor wires, replace outer door, and turn on
115-v power.
h. Blower will run for 90 seconds before beginning the call for heat
again.
i. Furnace should ignite normally.
Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that switches SW1-1 and SW1-6 are OFF and other setup
switches are set as desired. Verify that switches SW1-7 and SW1-8
for the blower OFF DELAY are set as desired per Table 14.
3. Verify that blower and burner access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instructions.
6. Review User’s Guide with owner.
7. Attach literature packet to furnace.
X- Indicated an allowable selection.
Table 12 – Cooling Airflow Adjustments from 1.5 to 6 Tons
AIR CONDITIONING TONS
(12,000 BTU/HR)
AIRFLOW (CFM) 070 MODEL 090 MODEL 110 & 135 MODELS
1-1/2 525
X
2
X
2 700 X
X
2
X
2-1/2 875 X X
X
2
3 1050
X
1
X X
3-1/2 1225 X
X
1
X
4 1400 X X
5 1750
X
1
6 2100 X
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
31
Table 13 – Air Delivery - CFM (With Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See Footnotes
1
and
2
)
Unit Size:36045C17 Clg/CF Switch Settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1070 1080 1085 1095 1095 1100 1095 1090 1080 1070
CF Switches SW3-3 SW3-2 SW3-1
Low-Clg Default: OFF OFF OFF 525 540 540 550 550
See Note
4
Cooling Airflow
(SW2)
Low-Cooling Airflow
(SW3)
OFF OFF ON 525 540 540 550 550
See Note
4
OFF ON OFF 700 720 715 730 735 745 745 745 735 725
OFF ON ON 885 905 920 925 920 910 905 900 895 885
ON OFF OFF 1070 1080 1085 1095 1095 1100 1095 1090 1080 1070
ON OFF ON 1250 1265 1275 1280 1275 1265 1255 1240 1205 1170
ON ON OFF 1425 1425 1410 1380 1340 1305 1270 1235 1200 1165
ON ON ON 1425 1425 1410 1380 1340 1305 1270 1235 1200 1165
Maximum Clg Airflow
2
1480 1445 1415 1380 1345 1310 1275 1235 1200 1165
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default: OFF OFF OFF 525 540 540 550 550
See Note
4
Continuous Fan
Airflow (SW3)
OFF OFF ON 525 540 540 550 550
See Note
4
OFF ON OFF 700 720 715 730 735 745 745 745 735 725
OFF ON ON 885 905 920 925 920 910 905 900 895 885
ON OFF OFF 1070 1080 1085 1095 1095 1100 1095 1090 1080 1070
ON OFF ON 1070 1080 1085 1095 1095 1100 1095 1090 1080 1070
ON ON OFF 1070 1080 1085 1095 1095 1100 1095 1090 1080 1070
ON ON ON 1070 1080 1085 1095 1095 1100 1095 1090 1080 1070
Heating (SW1)
High Heat Airflow
3
730 730 735 750 765 770 770 770 760 750
Low Heat Airflow
3
605 625 635 630 635 635 630 625 615 605
Unit Size: 36070C14 Clg/CF Switch Settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1050 1050 1050 1050 1050 1050 1045 1035 1020 1000
CF Switches SW3-3 SW3-2 SW3-1
Low-Clg Default: OFF OFF OFF 515 500 500 490 485
See Note
4
Cooling Airflow
(SW2)
Low-Cooling Airflow
(SW3)
OFF OFF ON 515 500 500 490 485
See Note
4
OFF ON OFF 690 680 675 680 675
See Note
4
OFF ON ON 875 875 875 870 865 855 850 835 825 820
ON OFF OFF 1050 1050 1050 1050 1050 1050 1045 1035 1020 1000
ON OFF ON 1220 1225 1225 1225 1225 1220 1205 1190 1185 1170
ON ON OFF 1220 1225 1225 1225 1225 1220 1205 1190 1185 1170
ON ON ON 1220 1225 1225 1225 1225 1220 1205 1190 1185 1170
Maximum Clg Airflow
2
1395 1400 1400 1400 1395 1385 1370 1340 1300 1245
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default: OFF OFF OFF 515 500 500 490 485
See Note
4
Continuous Fan
Airflow (SW3)
OFF OFF ON 515 500 500 490 485
See Note
4
OFF ON OFF 690 680 675 680 675
See Note
4
OFF ON ON 875 875 875 870 865 855 850 835 825 820
ON OFF OFF 1050 1050 1050 1050 1050 1050 1045 1035 1020 1000
ON OFF ON 1220 1225 1225 1225 1225 1220 1205 1190 1185 1170
ON ON OFF 1220 1225 1225 1225 1225 1220 1205 1190 1185 1170
ON ON ON 1220 1225 1225 1225 1225 1220 1205 1190 1185 1170
Heating (SW1)
High Heat Airflow
3
1160 1165 1175 1180 1180 1180 1180 1180 1180 1175
Low Heat Airflow
3
735 735 735 735 725
See Note
4
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
32
(SW1-5 and SW4-3 set to OFF, except as indicated. See Footnotes
1
and
2
)
Unit Size: 48070C17 Clg/CF Switch Settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1435 1435 1435 1420 1380 1345 1310 1270 1235 1200
CF Switches SW3-3 SW3-2 SW3-1
Low-Clg Default: OFF OFF OFF 705 715 720 720 715 705 700 690 680 665
Cooling Airflow
(SW2)
Low-Cooling Airflow
(SW3)
OFF OFF ON 530 535 530 520 505
See Note
4
OFF ON OFF 705 715 720 720 715 705 700 690 680 665
OFF ON ON 870 885 890 895 895 895 890 885 875 865
ON OFF OFF 1110 1110 1110 1105 1100 1090 1085 1075 1065 1050
ON OFF ON 1240 1240 1245 1245 1240 1235 1230 1225 1215 1210
ON ON OFF 1435 1435 1435 1420 1380 1345 1310 1270 1235 1200
ON ON ON 1435 1435 1435 1420 1380 1345 1310 1270 1235 1200
Maximum Clg Airflow
2
1510 1480 1445 1410 1375 1340 1305 1270 1235 1200
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default: OFF OFF OFF 805 800 795 790 775 765 750 735 715 700
Continuous Fan
Airflow (SW3)
OFF OFF ON 520 520 515 510 495
See Note
4
OFF ON OFF 635 630 625 620 605 595 580 565 550 535
OFF ON ON 805 800 795 790 775 765 750 735 715 700
ON OFF OFF 805 800 795 790 775 765 750 735 715 700
ON OFF ON 805 800 795 790 775 765 750 735 715 700
ON ON OFF 805 800 795 790 775 765 750 735 715 700
ON ON ON 805 800 795 790 775 765 750 735 715 700
Heating (SW1)
High Heat Airflow
3
1245 1250 1250 1240 1235 1230 1225 1215 1205 1200
Low Heat Airflow
3
1040 1040 1035 1030 1030 1020 1010 1000 990 980
Unit Size: 60070C21 Clg/CF Switch Settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1785 1815 1825 1825 1825 1820 1810 1805 1795 1755
CF Switches SW3-3 SW3-2 SW3-1
Low-Clg Default: OFF OFF OFF 855 905 925 950 970 970 960 955 970 965
Cooling Airflow
(SW2)
Low-Cooling Airflow
(SW3)
OFF OFF ON 670 735 765 775 790
See Note
4
OFF ON OFF 855 905 925 950 970 970 960 955 970 965
OFF ON ON 1040 1040 1050 1085 1085 1095 1100 1090 1080 1090
ON OFF OFF 1235 1255 1290 1300 1315 1310 1310 1310 1295 1285
ON OFF ON 1495 1475 1490 1490 1495 1490 1485 1470 1460 1455
ON ON OFF 1785 1815 1825 1825 1825 1820 1810 1805 1795 1755
ON ON ON 2145 2140 2135 2125 2110 2090 2040 1965 1875 1800
Maximum Clg Airflow
2
2225 2215 2205 2190 2150 2110 2045 1970 1880 1800
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default: OFF OFF OFF 855 905 925 950 970 970 960 955 970 965
Continuous Fan
Airflow (SW3)
OFF OFF ON 670 735 765 775 790
See Note
4
OFF ON OFF 855 905 925 950 970 970 960 955 970 965
OFF ON ON 1040 1040 1050 1085 1085 1095 1100 1090 1080 1090
ON OFF OFF 1040 1040 1050 1085 1085 1095 1100 1090 1080 1090
ON OFF ON 1040 1040 1050 1085 1085 1095 1100 1090 1080 1090
ON ON OFF 1040 1040 1050 1085 1085 1095 1100 1090 1080 1090
ON ON ON 1040 1040 1050 1085 1085 1095 1100 1090 1080 1090
Heating (SW1)
High Heat Airflow
3
1195 1215 1240 1250 1255 1270 1265 1260 1255 1245
Low Heat Airflow
3
1085 1090 1115 1135 1160 1160 1155 1150 1150 1140
Table 13 – Air Delivery - CFM (With Filter) (Continued)
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
33
(SW1-5 and SW4-3 set to OFF, except as indicated. See Footnotes
1
and
2
)
Unit Size: 48090C17 Clg/CF Switch Settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1350 1370 1390 1390 1400 1390 1380 1380 1360 1340
CF Switches SW3-3 SW3-2 SW3-1
Low-Clg Default: OFF OFF OFF 680 680 680 675 670
See Note
4
Cooling Airflow
(SW2)
Low-Cooling Airflow
(SW3)
OFF OFF ON 525 520 525 495 475
See Note
4
OFF ON OFF 680 680 680 675 670
See Note
4
OFF ON ON 815 845 845 855 850 850 845 835 820 805
ON OFF OFF 1005 1005 1015 1035 1040 1040 1035 1030 1025 1010
ON OFF ON 1190 1200 1200 1205 1205 1215 1205 1200 1185 1170
ON ON OFF 1350 1370 1390 1390 1400 1390 1380 1380 1360 1340
ON ON ON 1350 1370 1390 1390 1400 1390 1380 1380 1360 1340
Maximum Clg Airflow
2
1595 1600 1600 1600 1595 1555 1505 1465 1430 1390
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default: OFF OFF OFF 680 680 680 675 670
See Note
4
Continuous Fan
Airflow (SW3)
OFF OFF ON 525 520 525 495 475
See Note
4
OFF ON OFF 680 680 680 675 670
See Note
4
OFF ON ON 815 845 845 855 850 850 845 835 820 805
ON OFF OFF 1005 1005 1015 1035 1040 1040 1035 1030 1025 1010
ON OFF ON 1190 1200 1200 1205 1205 1215 1205 1200 1185 1170
ON ON OFF 1190 1200 1200 1205 1205 1215 1205 1200 1185 1170
ON ON ON 1190 1200 1200 1205 1205 1215 1205 1200 1185 1170
Heating (SW1)
High Heat Airflow
3
1190 1205 1210 1210 1210 1210 1210 1210 1210 1200
Low Heat Airflow
3
950 970 985 985 985 985 985 985 985 980
Unit Size: 60090C21 Clg/CF Switch Settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1785 1805 1815 1835 1840 1855 1860 1850 1845 1835
CF Switches SW3-3 SW3-2 SW3-1
Low-Clg Default: OFF OFF OFF 925 935 945 960 980 965 940 925 920 900
Cooling Airflow
(SW2)
Low-Cooling Airflow
(SW3)
OFF OFF ON 715 715 735 730 730
See Note
4
OFF ON OFF 925 935 945 960 980 965 940 925 920 900
OFF ON ON 1040 1045 1030 1055 1060 1045 1060 1045 1030 1005
ON OFF OFF 1295 1320 1285 1335 1350 1340 1350 1335 1310 1300
ON OFF ON 1505 1525 1480 1480 1490 1475 1465 1455 1450 1445
ON ON OFF 1785 1805 1815 1835 1840 1855 1860 1850 1845 1835
ON ON ON 2250 2265 2270 2265 2255 2245 2220 2175 2120 2060
Maximum Clg Airflow
2
2375 2375 2375 2365 2330 2285 2235 2185 2140 2075
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default: OFF OFF OFF 925 935 945 960 980 965 940 925 920 900
Continuous Fan
Airflow (SW3)
OFF OFF ON 715 715 735 730 730
See Note
4
OFF ON OFF 925 935 945 960 980 965 940 925 920 900
OFF ON ON 1040 1045 1030 1055 1060 1045 1060 1045 1030 1005
ON OFF OFF 1295 1320 1285 1335 1350 1340 1350 1335 1310 1300
ON OFF ON 1505 1525 1480 1480 1490 1475 1465 1455 1450 1445
ON ON OFF 1505 1525 1480 1480 1490 1475 1465 1455 1450 1445
ON ON ON 1505 1525 1480 1480 1490 1475 1465 1455 1450 1445
Heating (SW1)
High Heat Airflow
3
1590 1610 1605 1605 1600 1605 1610 1610 1615 1620
Low Heat Airflow
3
1425 1450 1440 1465 1470 1455 1450 1440 1435 1430
Table 13 – Air Delivery - CFM (With Filter) (Continued)
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
34
1. Nominal 350 CFM/ton cooling airflow is delivered with SW1-5 and SW4-3 set to OFF.
Set SW1-5 to ON for nominal 400 CFM/ton (+15% airflow).
Set SW4-3 to ON for nominal 325 CFM/ton (-7% airflow).
Set both SW1-5 and SW4-3 on ON for nominal 370 CFM/ton (+7% airflow).
This applies to Cooling and Low-Cooling airflow, but does not affect continuous fan airflow.
The above adjustments in airflow are subject to motor horsepower range/capacity.
2. Maximum cooling airflow is achieved when switches SW2-1, SW2-2, SW2-3 and SW1-5 are set to ON, and SW4-3 is set to OFF.
3. All heating CFM's are when comfort/efficiency adjustment switch (SW1-4) is set to OFF
4. Ductwork must be sized for high-heating CFM within the operational range of ESP. Operation within the blank areas of the chart is not recommended because high-heat operation will be
above 1.0 ESP.
5. All airflows on 21" casing size furnaces are 5% less on side return only installations.
(SW1-5 and SW4-3 set to OFF, except as indicated. See Footnotes
1
and
2
)
Unit Size: 60110C21 Clg/CF Switch Settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1750 1750 1750 1750 1750 1750 1750 1750 1740 1725
CF Switches SW3-3 SW3-2 SW3-1
Low-Clg Default:
OFF OFF OFF 875 875 875 875 875 See Note
4
Cooling Airflow
(SW2)
Low-Cooling Airflow
(SW3)
OFF OFF ON 700 700 700 700 700 See Note
4
OFF ON OFF 875 875 875 875 875 See Note
4
OFF ON ON 1050 1050 1050 1050 1050 See Note
4
ON OFF OFF 1225 1225 1225 1225 1225 1225 1225 1225 1225 1225
ON OFF ON 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400
ON ON OFF 1750 1750 1750 1750 1750 1750 1750 1750 1740 1725
ON ON ON 2100 2100 2100 2100 2090 2075 2055 2040 2005 1970
Maximum Clg Airflow
2
2200 2190 2190 2180 2155 2145 2125 2100 2080 2020
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default:
OFF OFF OFF 875 875 875 875 875 See Note
4
Continuous Fan
Airflow (SW3)
OFF OFF ON 700 700 700 700 700 See Note
4
OFF ON OFF 875 875 875 875 875 See Note
4
OFF ON ON 1050 1050 1050 1050 1050 See Note
4
ON OFF OFF 1225 1225 1225 1225 1225 1225 1225 1225 1225 1225
ON OFF ON 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400
ON ON OFF 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400
ON ON ON 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400
Heating (SW1)
High Heat Airflow
3
1460 1465 1475 1475 1475 1475 1475 1475 1465 1465
Low Heat Airflow
3
1275 1295 1315 1320 1320 1320 1320 1320 1320 1315
Unit Size: 66135C24 Clg/CF Switch Settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1750 1765 1765 1775 1780 1785 1785 1775 1770 1765
CF Switches SW3-3 SW3-2 SW3-1
Low-Clg Default: OFF OFF OFF 860 880 895 900 905 900 890 865 845 825
Cooling Airflow
(SW2)
Low-Cooling Airflow
(SW3)
OFF OFF ON 690 710 715 710 690 See Note
4
OFF ON OFF 860 880 895 900 905 900 890 865 845 825
OFF ON ON 1015 1050 1070 1080 1085 1095 1095 1090 1085 1075
ON OFF OFF 1185 1220 1245 1260 1270 1275 1280 1280 1285 1280
ON OFF ON 1400 1415 1420 1425 1425 1420 1415 1410 1400 1390
ON ON OFF 1750 1765 1765 1775 1780 1785 1785 1775 1770 1765
ON ON ON 2080 2095 2100 2110 2105 2115 2125 2115 2120 2090
Maximum Clg Airflow
2
2240 2255 2265 2270 2265 2255 2220 2175 2135 2085
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default: OFF OFF OFF 860 880 895 900 905 900 890 865 845 825
Continuous Fan
Airflow (SW3)
OFF OFF ON 690 710 715 710 690 See Note
4
OFF ON OFF 860 880 895 900 905 900 890 865 845 825
OFF ON ON 1015 1050 1070 1080 1085 1095 1095 1090 1085 1075
ON OFF OFF 1185 1220 1245 1260 1270 1275 1280 1280 1285 1280
ON OFF ON 1400 1415 1420 1425 1425 1420 1415 1410 1400 1390
ON ON OFF 1400 1415 1420 1425 1425 1420 1415 1410 1400 1390
ON ON ON 1400 1415 1420 1425 1425 1420 1415 1410 1400 1390
Heating (SW1)
High Heat Airflow
3
1825 1835 1850 1855 1860 1860 1855 1850 1845 1840
Low Heat Airflow
3
1645 1660 1670 1675 1675 1675 1675 1670 1665 1660
Table 13 – Air Delivery - CFM (With Filter) (Continued)
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
35
Table 14 – Furnace Setup Switch Description
A190151
A190150
Fig. 52 – Service Label
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
36
Table 15 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated Data Based on 22,000 Btuh High-Heat/14,500 Btuh for
Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft. (305 M) Above Sea Level)
ALTITUDE RANGE FT.
(M)
AVG. GAS HEAT
VALUE (BTUH/CU
FT.)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
USA
0 to
2000
(0 to 610)
900 42 3.5/1.5 42 3.6/1.6 42 3.7/1.6 41 3.5/1.5
925 42 3.3/1.4 42 3.4/1.5 42 3.5/1.5 42 3.7/1.6
950 43 3.8/1.7 42 3.3/1.4 42 3.4/1.5 42 3.5/1.5
975 43 3.6/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
1000 43 3.5/1.5 43 3.6/1.6 43 3.7/1.6 43 3.8/1.7
1025 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6
1050 44 3.6/1.6 43 3.2/1.4 43 3.4/1.5 43 3.5/1.5
1075 44 3.4/1.5 44 3.5/1.5 43 3.2/1.4 43 3.3/1.4
1100 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5 43 3.2/1.4
USA
2001 to
3000
(610 to
914)
800 42 3.4/1.5 42 3.5/1.5 42 3.6/1.6 42 3.7/1.6
825 42 3.2/1.4 42 3.3/1.4 42 3.4/1.5 42 3.5/1.5
850 43 3.7/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
875 43 3.5/1.5 43 3.6/1.6 43 3.7/1.6 43 3.8/1.7
900 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6
925 44 3.5/1.5 43 3.2/1.4 43 3.3/1.4 43 3.4/1.5
950 44 3.4/1.5 44 3.5/1.5 44 3.6/1.6 43 3.2/1.4
975 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5
1000 45 3.7/1.6 45 3.8/1.7 44 3.2/1.4 44 3.4/1.5
USA
3001 to
4000
(914 to
1219)
775 42 3.2/1.4 42 3.3/1.4 42 3.4/1.5 42 3.5/1.5
800 43 3.6/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
825 43 3.4/1.5 43 3.5/1.5 43 3.7/1.6 43 3.8/1.6
850 43 3.2/1.4 43 3.3/1.4 43 3.4/1.5 43 3.6/1.5
875 44 3.5/1.5 44 3.6/1.6 43 3.3/1.4 43 3.4/1.5
900 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5 43 3.2/1.4
925 45 3.8/1.6 44 3.2/1.4 44 3.3/1.5 44 3.4/1.5
950 46 3.8/1.6 45 3.7/1.6 45 3.8/1.7 44 3.3/1.4
USA
4001 to
5000
(1219 to
1524)
750 43 3.6/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
775 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6 43 3.8/1.6
800 43 3.2/1.4 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5
825 44 3.4/1.5 44 3.6/1.5 43 3.2/1.4 43 3.3/1.4
850 44 3.2/1.4 44 3.4/1.5 44 3.5/1.5 44 3.6/1.6
875 45 3.7/1.6 45 3.8/1.7 44 3.3/1.4 44 3.4/1.5
900 46 3.7/1.6 46 3.8/1.7 45 3.7/1.6 44 3.2/1.4
925 46 3.5/1.5 46 3.6/1.6 46 3.7/1.6 46 3.8/1.7
USA
5001 to
6000
(1524 to
1829)
725 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6 43 3.7/1.6
750 43 3.2/1.4 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5
775 44 3.4/1.5 44 3.5/1.5 43 3.2/1.4 43 3.3/1.4
800 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5
825 46 3.8/1.7
45 3.8/1.6 44 3.2/1.4 44 3.3/1.4
850 46 3.6/1.6 46 3.7/1.6 46 3.8/1.7 45 3.8/1.6
875 47 3.8/1.7 46 3.5/1.5 46 3.6/1.6 46 3.7/1.6
900 47 3.6/1.6 47 3.8/1.6 46 3.4/1.5 46 3.5/1.5
USA
6001 to
7000
(1829 to
2134)
675 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6 43 3.7/1.6
700 44 3.6/1.6 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5
725 44 3.4/1.5 44 3.5/1.5 44 3.6/1.6 43 3.2/1.4
750 45 3.8/1.7 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5
775 46 3.7/1.6 45 3.7/1.6 45 3.8/1.7 44 3.2/1.4
800 46 3.5/1.5 46 3.6/1.6 46 3.8/1.6 45 3.7/1.6
825 47 3.7/1.6 46 3.4/1.5 46 3.5/1.5 46 3.6/1.6
850 47 3.5/1.5 47 3.6/1.6 47 3.8/1.6 46 3.4/1.5
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
37
* Orifice numbers 43 are factory installed
USA
7001 to
8000
(2134 to
2438)
650 44 3.6/1.6 43 3.2/1.4 43 3.4/1.5 43 3.5/1.5
675 44 3.3/1.5 44 3.5/1.5 44 3.6/1.6 43 3.2/1.4
700 45 3.8/1.6 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5
725 46 3.7/1.6 46 3.8/1.7 45 3.7/1.6 44 3.2/1.4
750 46 3.4/1.5 46 3.6/1.5 46 3.7/1.6 46 3.8/1.6
775 47 3.6/1.6 47 3.8/1.6 46 3.4/1.5 46 3.6/1.5
800 47 3.4/1.5 47 3.5/1.5 47 3.7/1.6 47 3.8/1.6
825 48 3.7/1.6 48 3.8/1.6 47 3.4/1.5 47 3.6/1.5
USA
8001 to
9000
(2438 to
2743)
625 44 3.3/1.5 44 3.5/1.5 44 3.6/1.6 43 3.2/1.4
650 45 3.7/1.6 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5
675 46 3.6/1.6 46 3.8/1.6 45 3.7/1.6 45 3.8/1.7
700 47 3.8/1.7 46 3.5/1.5 46 3.6/1.6 46 3.7/1.6
725 47 3.6/1.6 47 3.7/1.6 47 3.8/1.7 46 3.5/1.5
750 48 3.8/1.7 47 3.5/1.5 47 3.6/1.6 47 3.7/1.6
775 48 3.6/1.5 48 3.7/1.6 48 3.8/1.7 47 3.5/1.5
USA
9001 to
10,000
2743 to
3048)
600 45 3.7/1.6 45 3.8/1.7 44 3.3/1.4 44 3.4/1.5
625 46 3.6/1.6 46 3.7/1.6 46 3.8/1.7 45 3.8/1.6
650 47 3.8/1.6 46 3.4/1.5 46 3.6/1.5 46 3.7/1.6
675 47 3.5/1.5 47 3.6/1.6 47 3.7/1.6 46 3.4/1.5
700 48 3.7/1.6 48 3.8/1.7 47 3.5/1.5 47 3.6/1.6
725 48 3.5/1.5 48 3.6/1.6 48 3.7/1.6 48 3.8/1.7
Table 15 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated Data Based on 22,000 Btuh High-Heat/14,500 Btuh for
Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft. (305 M) Above Sea Level) (Continued)
ALTITUDE RANGE FT.
(M)
AVG. GAS HEAT
VALUE (BTUH/CU
FT.)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
Table 16 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated Data Based on 21,000 Btuh High-Heat/14,500 Btuh
for Low-Heat Per Burner, Derated 4 Percent for Each 1000 Ft. (305 M) Above Sea level)
ALTITUDE RANGE FT.
(M)
AVG. GAS HEAT
VALUE (BTUH/CU
FT.)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
USA
0 to
2000
(0 to 610)
900 42 3.2/1.5 42 3.3/1.6 42 3.4/1.6 42 3.5/1.7
925 43 3.7/1.8 43 3.8/1.8 42 3.2/1.5 42 3.3/1.6
950 43 3.5/1.7 43 3.6/1.7 43 3.7/1.8 43 3.8/1.8
975 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7 43 3.7/1.7
1000 44 3.6/1.7 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7
1025 44 3.4/1.6 44 3.6/1.7 43 3.2/1.5 43 3.3/1.6
1050 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
1075 45 3.8/1.8 44 3.2/1.5 44 3.3/1.6 44 3.4/1.6
1100 46 3.8/1.8 45 3.7/1.8 44 3.2/1.5 44 3.3/1.6
USA
2001 to
3000
(610 to
914)
800 43 3.8/1.8 42 3.2/1.5 42 3.3/1.6 42 3.4/1.6
825 43 3.5/1.7 43 3.7/1.7 43 3.8/1.8 42 3.2/1.5
850 43 3.3/1.6 43 3.5/1.6 43 3.6/1.7 43 3.7/1.8
875 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7
900 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6
925 44 3.2/1.5 44 3.3/1.6 44 3.5/1.6 44 3.6/1.7
950 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
975 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8 44 3.2/1.5
1000 46 3.5/1.7 46 3.6/1.7 46 3.8/1.8 45 3.7/1.8
USA
3001 to
4000
(914 to
1219)
775 43 3.5/1.7 43 3.7/1.7 43 3.8/1.8 42 3.2/1.5
800 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7 43 3.7/1.7
825 44 3.6/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
850 44 3.4/1.6 44 3.5/1.7 44 3.6/1.7 43 3.2/1.5
875 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7
900 46 3.8/1.8 45 3.8/1.8 44 3.2/1.5 44 3.3/1.6
925 46 3.6/1.7 46 3.7/1.8 45 3.7/1.8 45 3.8/1.8
950 46 3.4/1.6 46 3.5/1.7 46 3.7/1.7 46 3.8/1.8
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
38
* Orifice numbers 43 are factory installed
SERVICE AND MAINTENANCE PROCEDURES
Untrained personnel can perform basic maintenance functions such as
cleaning and replacing air filters. All other operations must be performed
by trained service personnel. A qualified service person should inspect
the furnace once a year.
USA
4001 to
5000
(1219 to
1524)
750 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7 43 3.6/1.7
775 44 3.6/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
800 44 3.3/1.6 44 3.4/1.6 44 3.6/1.7 43 3.2/1.5
825 45 3.8/1.8 44 3.2/1.5 44 3.4/1.6 44 3.5/1.6
850 46 3.8/1.8 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6
875 46 3.5/1.7 46 3.7/1.7 46 3.8/1.8 45 3.7/1.8
900 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8
925 47 3.6/1.7 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7
USA
5001 to
6000
(1524 to
1829)
725 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
750 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
775 45 3.7/1.8 44 3.2/1.5 44 3.3/1.6 44 3.4/1.6
800 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8 44 3.2/1.5
825 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8
850 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7
875 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6
900 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7 47 3.7/1.7
USA
6001 to
7000
(1829 to
2134)
675 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
700 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
725 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
750 46 3.6/1.7 46 3.8/1.8 45 3.7/1.8 45 3.8/1.8
775 46 3.4/1.6 46 3.5/1.7 46 3.6/1.7 46 3.8/1.8
800 47 3.6/1.7 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7
825 47 3.4/1.6 47 3.5/1.7 47 3.6/1.7 47 3.8/1.8
850 48 3.7/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7
USA
7001 to
8000
(2134 to
2438)
650 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
675 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
700 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8
725 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8
750 47 3.5/1.7 47 3.7/1.8 47 3.8/1.8 46 3.5/1.6
775 48 3.8/1.8 47 3.4/1.6 47 3.6/1.7 47 3.7/1.7
800 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8 47 3.4/1.6
825 48 3.3/1.6 48 3.5/1.6 48 3.6/1.7 48 3.7/1.8
USA
8001 to
9000
(2438 to
2743)
625 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
650 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8
675 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7 46 3.7/1.7
700 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6
725 48 3.7/1.8 48 3.8/1.8 47 3.5/1.7 47 3.6/1.7
750 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8
775 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7
USA
9001 to
10,000
(2743 to
3048)
600 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.7/1.8
625 47 3.7/1.8 47
3.8/1.8 46 3.5/1.7 46 3.6/1.7
650 47 3.4/1.6 47 3.6/1.7 47 3.7/1.8 47 3.8/1.8
675 48 3.6/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7
700 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8
725 49 3.7/1.8 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7
Table 16 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated Data Based on 21,000 Btuh High-Heat/14,500 Btuh
for Low-Heat Per Burner, Derated 4 Percent for Each 1000 Ft. (305 M) Above Sea level) (Continued)
ALTITUDE RANGE FT.
(M)
AVG. GAS HEAT
VALUE (BTUH/CU
FT.)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
Orifice No.
Manifold
Pressure
High/Low
WARNING
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
The ability to properly perform maintenance on this equipment requires
certain knowledge, mechanical skills, tools, and equipment. If you do
not possess these, do not attempt to perform any maintenance on this
equipment other than those procedures recommended in the User’s
Manual.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
39
GENERAL
These instructions are written as if the furnace is installed in an upflow
application. An upflow furnace application is where the blower is
located below the combustion and controls section of the furnace, and
conditioned air is discharged upward. Since this furnace can be installed
in any of 4 positions, see in Fig. 6, you must revise your orientation to
component location accordingly.
Electrical Controls and Wiring
The electrical ground and polarity for 115-v wiring must be properly
maintained. See Fig. 24 for field wiring information, and see Fig. 56 in
the Wiring Diagram section for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the control
will flash rapidly and prevent the furnace from heating. The control
system also requires an earth ground for proper operation of the control
and flame-sensing electrode.
The 24-v circuit contains an automotive-type, 3-amp. fuse located on the
control, see Fig. 35. Any shorts of the 24-v wiring during installation,
service, or maintenance will cause this fuse to blow. If fuse replacement
is required, use ONLY a 3-amp. fuse. The control LED will display
status code 24 when fuse needs to be replaced.
Proper instrumentation is required to service electrical controls. The
control in this furnace is equipped with a Status Code LED
(Light-Emitting Diode) to aid in installation, servicing, and
troubleshooting. Status codes can be viewed at the sight glass in blower
access door. The amber furnace control LED is either ON continuously,
rapid flashing, or a code composed of 2 digits. The first digit is the
number of short flashes, the second digit is the number of long flashes.
For an explanation of status codes, refer to service label located on
blower access door (also on Fig. 52), and the troubleshooting guide
which can be obtained from your distributor.
See the brief Troubleshooting Guide, see Fig. 57.
For 2-Stage Variable Speed ECM Controls the stored status codes will
NOT be erased from the control memory, when 115- or 24-v power is
interrupted. The control will store up to the last 7 Status Codes in order
of occurrence.
1. To retrieve status codes, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all
blower-OFF delays must be completed.
a. Leave 115-v power to furnace turned on.
b. Remove outer access door.
c. Look into blower access door sight glass for current LED status.
d. Remove blower access door.
NOTE: The Status Codes cannot be retrieved by disconnecting the limit
switch or draft safeguard switch. To retrieve Status Codes, follow the
procedure below.
2. Turn Setup Switch, SW1-1 “ON.”
3. Manually close blower access door switch.
4. Control will flash up to 7 Status Codes.
5. The last Status Code, or 8th Code, will be code 11.
6. Turn SW1-1 “OFF.”
7. The Amber LED will be continuously lit which indicates proper
operation.
8. Release blower access door switch, install blower access door and
replace outer door, or refer to the SERVICE label on the front of the
blower access door for more information.
Component Self-Test
Component Test can ONLY be initiated by performing the following:
1. Remove outer access door.
2. Remove blower access door.
3. Remove the wire from the “R” terminal of the control board.
4. Turn Setup Switch, SW-1-6 “ON.”
5. Manually close blower access door switch.
Blower access door switch opens 115-v power to control. No component
operation can occur unless switch is closed. Caution must be taken when
manually closing this switch for service purposes.
6. Component Test sequence will function as follows:
a. Inducer motor starts on high-speed and continues to run until
Step (d.) of component test sequence.
b. Hot surface igniter is energized for 15 sec, then de-energized.
c. Blower operates for 10 sec, then turns off.
d. Inducer motor goes to low-speed for 10 seconds, then turns off.
CAUTION
!
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental pollution.
Remove and recycle all components or materials (i.e. oil, refrigerant,
control board, etc.) before unit final disposal.
WARNING
!
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death,
or property damage.
Before installing, modifying, or servicing system, main electrical
disconnect switch must be in the OFF position and install a lockout tag.
There may be more than one disconnect switch. Lock out and tag
switch with a suitable warning label. Verify proper operation after
servicing.
CAUTION
!
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper furnace operation
or failure of furnace.
Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
There may be more than one electrical supply to the furnace. Check
accessories and cooling unit for additional electrical supplies that must
be shut off during furnace servicing. Lock out and tag switch with a
suitable warning label.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115-v power to furnace control. No
component operation can occur unless switch is closed. Exercise
caution to avoid electrical shock from exposed electrical components
when manually closing this switch for service purposes.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
40
e. After component test is completed, one or more status codes 11,
25 or 41 will flash. See component test section of service label
for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1-6 OFF then
back ON.
f. Turn setup switch SW1-6 OFF.
7. RELEASE BLOWER ACCESS DOOR SWITCH, reattach wire to
“R” terminal on furnace control board, replace blower access door,
and replace outer access door.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible furnace
failure, periodic maintenance must be performed on this furnace.
Consult your local dealer about proper frequency of maintenance and the
availability of a maintenance contract.
The minimum maintenance on this furnace is as follows:
1. Check and clean air filter each month or more frequently if
required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heating and
cooling season. Clean as necessary.
3. Check electrical connections for tightness and controls for proper
operation each heating season. Service as necessary.
4. Inspect burner compartment before each heating season for rust,
corrosion, soot or excessive dust. If necessary, have furnace and
burner serviced by a qualified service agency.
5. Inspect the vent pipe/vent system before each heating season for
rust, corrosion, water leakage, sagging pipes or broken fittings.
Have vent pipes/vent system serviced by a qualified service agency.
6. Inspect any accessories attached to the furnace such as a humidifier
or electronic air cleaner. Perform any service or maintenance to the
accessories as recommended in the accessory instructions.
Cleaning and/or Replacing Air Filter
The air filter arrangement will vary depending on the application.
NOTE: If the filter has an airflow direction arrow, the arrow must point
towards the blower.
Media Cabinet Filter Procedures:
Perform the following procedure to clean or replace a media cabinet
filter:
1. Turn off electrical supply to furnace before removing filter access
door.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable 3/4-in. (19 mm) filter, clean
filter by spraying cold tap water through filter in opposite direction
of airflow. Rinse filter and let dry. Oiling or coating of the filter is
not recommended. See Table 17 for size information.
5. If equipped with factory-specified disposable media filter, replace
only with media filter having the same part number and size. For
expandable replacement media, refer to the instructions included
with the replacement media.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
Never store anything on, near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners,
or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds,
plastic or plastic containers, gasoline, kerosene, cigarette lighter
fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other
paper products. Exposure to these materials could lead to
corrosion of the heat exchangers.
WARNING
!
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
Never operate furnace without a filter or with filter access door
removed.
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Turn off the gas and electrical supplies to the furnace and install lockout
tag before performing any maintenance or service. Follow the operating
instructions on the label attached to the furnace.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts, and servicing furnaces.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts, and servicing furnaces.
Table 17 – Filter Size Information - In. (mm)
FURNACE
CASING WIDTH
FILTER SIZE
FILTER TYPE
SIDE
RETURN
BOTTOM
RETURN
14-1/2 (368)
16 x 25 x 3/4
(406 x 635 x 19)
14 x 25 x 3/4
(356 x 635 x 19)
Washable
*
*. Recommended
17-1/2 (445)
16 x 25 x 3/4
(406 x 635 x 19)
16 x 25 x 3/4
(406 x 635 x 19)
Washable
*
21 (533)
16 x 25 x 3/4
(406 x 635 x 19)
20 x 25 x 3/4
(508 x 635 x 19)
Washable
*
24 (610)
16 x 25 x 3/4
(406 x 635 x 19)
24 x 25 x 3/4
(610 x 635 x 19)
Washable
*
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
41
Blower Motor and Wheel
To ensure long life and high efficiency, clean accumulated dirt and
grease from blower wheel and motor annually.
The steps given here for the blower motor and wheel should be
performed by a qualified service agency.
The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the absence of
oil ports on each end of the motor.
NOTE: The blower wheel should not be dropped or bent as balance will
be affected.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove outer door.
3. For downflow or horizontal furnaces having vent pipes within the
furnace that pass in front of the blower access door:
a. Disconnect vent connector from furnace vent elbow.
b. Disconnect and remove short piece of vent pipe from within
furnace.
4. Remove 2 screws from blower access door and remove blower
access door.
5. All factory wires can be left connected, but field thermostat
connections may need to be disconnected depending on their length
and routing.
6. Remove 2 screws holding blower assembly to blower deck and
slide blower assembly out of furnace.
7. Clean blower wheel and motor using a vacuum with soft brush
attachment. Blower wheel blades may be cleaned with a small paint
or flux brush. Do not remove or disturb balance weights (clips) on
blower wheel blades.
8. Vacuum any loose dust from blower housing, wheel and motor.
9. If a greasy residue is present on blower wheel, remove wheel from
the blower housing and wash it with an appropriate degreaser.
NOTE: Before disassembly, mark blower mounting arms, motor, and
blower housing so motor and each arm is positioned at the same location
during reassembly.
To remove wheel:
a. Disconnect ground wire attached to blower housing.
b. Remove screws securing cutoff plate and remove cutoff plate
from housing.
c. Loosen set screw holding blower wheel on motor shaft (160+/-20
in.-lb. when assembling).
d. Remove bolts holding motor to blower housing and slide motor
out of wheel (40+/-10 in.-lb. when reassembling).
e. Remove blower wheel from housing.
f. Clean wheel and housing.
10. Reassemble motor and blower by reversing steps 9a, through 9e. Be
sure to reattach ground wire to the blower housing.
11. Verify that blower wheel is centered in blower housing and set
screw contacts the flat portion of the motor shaft. Loosen set screw
on blower wheel and reposition if necessary.
12. Spin the blower wheel by hand to verify that the wheel does not rub
on the housing.
13. Reinstall blower assembly in furnace.
14. Reinstall 2 screws securing blower assembly to blower deck.
15. Reconnect blower leads to furnace control. Refer to furnace wiring
diagram, and connect thermostat leads if previously disconnected.
16. To check blower for proper rotation:
a. Turn on electrical supply.
b. Manually close blower access door switch.
NOTE: If R-W/W1 thermostat terminals are jumpered at the time
blower access door switch is closed, blower will run for 90 sec before
beginning a heating cycle.
c. Perform component self-test as shown at the bottom of the
SERVICE label, located on the front of blower access door.
d. Verify blower is rotating in the correct direction
17. If furnace is operating properly, RELEASE BLOWER ACCESS
DOOR SWITCH. Remove any jumpers or reconnect any
disconnected thermostat leads. Replace blower access door.
18. Downflow or horizontal furnaces with vent pipe through furnace
only:
a. Install and connect short piece of vent pipe inside furnace to
existing vent.
b. Connect vent connector to vent elbow.
19. Reinstall outer door.
20. Turn on gas supply and cycle furnace through one complete heating
and cooling cycle. Verify the furnace temperature rise as shown in
Adjustments Section. Adjust temperature rise as shown in
Adjustments Section. If outdoor temperature is below 70°F, turn off
circuit breaker to outdoor unit before running furnace in the cooling
cycle. Turn outdoor circuit breaker on after completing cooling
cycle.
Cleaning Heat Exchanger
The steps given here for cleaning heat exchangers should be performed
by a qualified service agency.
NOTE: If the heat exchangers get a heavy accumulation of soot and
carbon, they should be replaced rather than trying to clean them
thoroughly. A build-up of soot and carbon indicates that a problem exists
which needs to be corrected, such as improper adjustment of manifold
pressure, insufficient or poor quality combustion air, incorrect size or
damaged manifold orifice(s), improper gas, or a restricted heat
exchanger. Action must be taken to correct the problem.
If it becomes necessary to clean the heat exchangers because of dust or
corrosion, proceed as follows:
1. Turn OFF gas and electrical power to furnace.
2. Remove outer access door.
3. Disconnect vent connector from furnace vent elbow.
4. For downflow or horizontal furnace having an internal vent pipe,
remove internal vent pipe within the casing.
5. Disconnect wires to the following components. Mark wires to aid in
reconnection (be careful when disconnecting wires from switches
because damage may occur):
a. Draft safeguard switch.
b. Inducer motor.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access door switch opens 115-v power to control. No
component operation can occur unless switch is closed. Caution must
be taken when manually closing this switch for service purposes.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115-v power to furnace control. No
component operation can occur unless switch is closed. Exercise
caution to avoid electrical shock from exposed electrical components
when manually closing this switch for service purposes.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
42
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing electrode.
h. Flame rollout switches.
6. Remove screws that fasten the collector box assembly to the cell
panel. Be careful not to damage the collector box. Inducer assembly
and elbow need not be removed from collector box.
7. Disconnect gas line from gas manifold.
8. Remove the four screws that attach the burner assembly to the cell
panel. The gas valve and individual burners need not be removed
from support assembly. Remove NOx baffles, if installed.
NOTE: Be very careful when removing burner assembly to avoid
breaking igniter. See Fig. 53 - Fig. 54 for correct igniter location.
A05026
Fig. 53 – Igniter Position - Top View
A05025
Fig. 54 – Igniter Position - Side View
NOTE: The materials needed in Step 9 can usually be purchased at local
hardware stores.
9. Using a field-provided 25-caliber rifle cleaning brush; a 36-in. (914
mm) long, 1/4-in. (6 mm) diameter steel spring cable; and a
variable speed drill, do the following:
a. Remove metal screw fitting from wire brush to allow insertion
into cable.
b. Insert the twisted wire end of brush into end of spring cable, and
crimp tight with crimping tool or crimp by striking with
ball-peen hammer. TIGHTNESS IS VERY IMPORTANT. After
crimping:
(1.) Attach variable-speed, reversible drill to the end of spring
cable (end opposite brush).
(2.) Insert brush end of cable into the outlet opening of cell and
slowly rotate with drill, see Fig. 55. DO NOT force cable.
Gradually insert cable into upper pass of cell.
A91252
Fig. 55 – Cleaning Heat Exchanger Cell
(3.) Work cable in and out of cell 3 or 4 times to obtain
sufficient cleaning. DO NOT pull cable with great force.
Reverse drill and gradually work cable out.
(4.) Insert brush end of cable in burner inlet opening of cell, and
proceed to clean 2 lower passes of cell in same manner as
upper pass.
(5.) Repeat foregoing procedures until each cell in furnace has
been cleaned.
(6.) Using vacuum cleaner, remove residue from each cell.
(7.) Using vacuum cleaner with soft brush attachment, clean
burner assembly.
(8.) Clean flame sensor with fine steel wool.
(9.) Install NOx baffles (if removed).
(10.)Reinstall burner assembly. Center burners in cell openings.
10. Remove old sealant from cell panel and collector box flange.
11. Spray releasing agent on the heat exchanger cell panel where
collector box assembly contacts cell panel.
NOTE: A releasing agent such as cooking spray or equivalent (must not
contain corn or canola oil, aromatic or halogenated hydrocarbons or
inadequate seal may occur) and RTV sealant (G.E. 162, 6702, or
Dow-Corning 738) are needed before starting installation. DO NOT
substitute any other type of RTV sealant. G.E. 162 (P771-9003) is
available through RCD in 3-oz tubes.
12. Apply new sealant to flange of collector box and attach to cell panel
using existing screws, making sure all screws are secure.
13. Reconnect wires to the following components (Use connection
diagram on wiring label, if wires were not marked for reconnection
locations.):
a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing electrode.
h. Flame rollout switches.
14. Reinstall internal vent pipe, if applicable.
15. Reinstall vent connector on furnace vent elbow. Securely fasten
vent connector to vent elbow with 2 field-supplied,
corrosion-resistant, sheet metal screws located 180° apart.
16. Replace blower access door only if it was removed.
17. Set thermostat above room temperature and check furnace for
proper operation.
18. Verify blower airflow and speed changes between heating and
cooling.
1-7/8
(47.6 mm)
9/32”
7.1mm
5/16”
7.9mm
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
43
19. Check for gas leaks.
SEQUENCE OF OPERATION
NOTE: Furnace control must be grounded for proper operation or else
control will lock out. Control is grounded through green/yellow wire
routed to gas valve and burner box screw. Using the schematic diagram
in Fig. 56, follow the sequence of operation through the different modes.
Read and follow the wiring diagram very carefully.
NOTE: If a power interruption occurs during a call for heat (W/W1 or
W/W1-and-W2), the control will start a 90-second blower-only ON
period two seconds after power is restored, if the thermostat is still
calling for gas heating. The amber LED light will flash code 12 during
the 90-second period, after which the LED will be ON continuous, as
long as no faults are detected. After the 90-second period, the furnace
will respond to the thermostat normally.
The blower door must be installed for power to be conducted through the
blower door interlock switch ILK to the furnace control CPU,
transformer TRAN, inducer motor IDM, blower motor BLWM,
hot-surface igniter HSI, and gas valve GV.
1. Perfect Heat
®
Technology - Two-Stage Heating (Adaptive
Mode) with Single-Stage Thermostat.
See Fig. 28 - Fig. 34 for thermostat connections.
NOTE: The low-heat only switch SW1-2 selects either the low-heat
only operation mode when ON, (see item 2. below) or the adaptive
heating mode when OFF in response to a call for heat, see Table 14.)
When the W2 thermostat terminal is energized it will always cause
high-heat operation when the R-to-W circuit is closed, regardless of the
setting of the low-heat only switch. This furnace can operate as a
two-stage furnace with a single-stage thermostat because the furnace
control CPU includes a programmed adaptive sequence of controlled
operation, which selects low-heat or high-heat operation. This selection
is based upon the stored history of the length of previous gas-heating
periods of the single-stage thermostat.
The furnace will start up in either low- or high-heat. If the furnace starts
up in low-heat, the control CPU determines the low-heat on-time (from 0
to 16 minutes) which is permitted before switching to high-heat.
If the power is interrupted, the stored history is erased and the control
CPU will select low-heat for up to 16 minutes and then switch to
high-heat, as long as the thermostat continues to call for heat.
Subsequent selection is based on stored history of the thermostat cycle
times.
The wall thermostat “calls for heat”, closing the R-to-W circuit. The
furnace control performs a self-check, verifies the low-heat and
high-heat pressure switch contacts LPS and HPS are open, and starts the
inducer motor IDM in high-speed.
a. Inducer Prepurge Period
(1.) If the furnace control CPU selects low-heat operation the
inducer motor IDM comes up to speed, the low-heat
pressure switch LPS closes, and the furnace control CPU
begins a 15-second prepurge period. If the low-heat pressure
switch LPS fails to remain closed, the inducer motor IDM
will remain running at high-speed. After the low-heat
pressure switch re-closes, the furnace control CPU will
begin a 15-second prepurge period, and continue to run the
inducer motor IDM at high-speed.
(2.) If the furnace control CPU selects high-heat operation, the
inducer motor IDM remains running at high-speed, and the
high-heat pressure switch relay HPSR is de-energized to
close the NC contact. When sufficient pressure is available
the high-heat pressure switch HPS closes, and the high-heat
gas valve solenoid GV-HI is energized. The furnace control
CPU begins a 15-second prepurge period after the low-heat
pressure switch LPS closes. If the high-heat pressure switch
HPS fails to close and the low-heat pressure switch LPS
closes, the furnace will operate at low-heat gas flow rate
until the high-heat pressure switch closes for a maximum of
2 minutes after ignition.
b. Igniter Warm-Up -At the end of the prepurge period, the
Hot-Surface Igniter HSI is energized for a 17-second igniter
warm-up period.
c. Trial-For-Ignition Sequence -When the igniter warm-up period
is completed the main gas valve relay contact GVR closes to
energize the gas valve solenoid GV-M. The gas valve solenoid
GV-M permits gas flow to the burners where it is ignited by the
HSI. Five seconds after the GVR closes, a 2-second flame
proving period begins. The HSI igniter will remain energized
until the flame is sensed or until the 2-second flame proving
period begins. If the furnace control CPU selects high-heat
operation, the high-heat gas valve solenoid GV-HI is also
energized.
d. Flame-Proving - When the burner flame is proved at the
flame-proving sensor electrode FSE, the inducer motor IDM
switches to low-speed unless the furnace is operating in
high-heat, and the furnace control CPU begins the blower-ON
delay period and continues to hold the gas valve GV-M open. If
the burner flame is not proved within two seconds, the control
CPU will close the gas valve GV-M, and the control CPU will
repeat the ignition sequence for up to three more
Trials-For-Ignition before going to Ignition-Lockout. Lockout
will be reset automatically after three hours, or by momentarily
interrupting 115 vac power to the furnace, or by interrupting 24
vac power at SEC1 or SEC2 to the furnace control CPU (not at
W/W1, G, R, etc.). If flame is proved when flame should not be
present, the furnace control CPU will lock out of Gas-Heating
mode and operate the inducer motor IDM on high speed until
flame is no longer proved.
e. Blower-On delay - If the burner flame is proven the blower-ON
delays for low-heat and high-heat are as follows:
Low-Heat - 45 seconds after the gas valve GV-M is opened the blower
motor BLWM is turned ON at low-heat airflow.
High-Heat - 25 seconds after the gas valve GV-M is opened the BLWM
is turned ON at high-heat airflow. Simultaneously, the humidifier
terminal HUM and electronic air cleaner terminal EAC-1 are energized
and remain energized throughout the heating cycle.
f. Switching from Low- to High-Heat - If the furnace control
CPU switches from low-heat to high-heat, the furnace control
CPU will switch the inducer motor IDM speed from low to high.
The high-heat pressure switch relay HPSR is de-energized to
close the NC contact. When sufficient pressure is available the
high-heat pressure switch HPS closes, and the high-heat gas
valve solenoid GV-HI is energized. The blower motor BLWM
will transition to high-heat airflow five seconds after the furnace
control CPU switches from low-heat to high-heat.
g. Switching from High- to Low-Heat -The furnace control CPU
will not switch from high-heat to low-heat while the thermostat
R-to-W circuit is closed when using a single-stage thermostat.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas
leaks with an open flame. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections. A
fire or explosion may result causing property damage, personal injury
or loss of life.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
44
h. Blower-Off Delay -When the thermostat is satisfied, the R to W
circuit is opened, de-energizing the gas valve GV-M, stopping
gas flow to the burners, and de-energizing the humidifier
terminal HUM. The inducer motor IDM will remain energized
for a 5-second post-purge period. The blower motor BLWM and
air cleaner terminal EAC-1 will remain energized at low-heat
airflow or transition to low-heat airflow for 90, 120, 150, or 180
seconds (depending on selection at blower-OFF delay switches).
The furnace control CPU is factory-set for a 120-second
blower-OFF delay.
2. Two-Stage Thermostat and Two-Stage Heating
See Fig. 28 - Fig. 34 for thermostat connections.
NOTE: In this mode the low-heat only switch SW1-2 must be ON to
select the low-heat only operation mode in response to closing the
thermostat R-to-W1 circuit. Closing the thermostat R-to- W1-and-W2
circuits always causes high-heat operation, regardless of the setting of
the low-heat only switch.
The wall thermostat “calls for heat”, closing the R-to-W1 circuit for
low-heat or closing the R-to-W1-and-W2 circuits for high-heat. The
furnace control performs a self-check, verifies the low-heat and
high-heat pressure switch contacts LPS and HPS are open, and starts the
inducer motor IDM in high-speed.
The start up and shut down functions and delays described in item 1.
above apply to the 2-stage heating mode as well, except for switching
from low- to high-Heat and vice versa.
a. Switching from Low- to High-Heat - If the thermostat R-to-W1
circuit is closed and the R-to-W2 circuit closes, the furnace
control CPU will switch the inducer motor IDM speed from low
to high. The high-heat pressure switch relay HPSR is
de-energized to close the NC contact. When sufficient pressure is
available the high-heat pressure switch HPS closes, and the
high-heat gas valve solenoid GV-HI is energized. The blower
motor BLWM will transition to high-heat airflow five seconds
after the R-to-W2 circuit closes.
b. Switching from High- to Low-Heat -If the thermostat R-to- W2
circuit opens, and the R-to-W1 circuit remains closed, the
furnace control CPU will switch the inducer motor IDM speed
from high to low. The high-heat pressure switch relay HPSR is
energized to open the NC contact and de-energize the high-heat
gas valve solenoid GV-HI. When the inducer motor IDM reduces
pressure sufficiently, the high-heat pressure switch HPS will
open. The gas valve solenoid GV-M will remain energized as
long as the low-heat pressure switch LPS remains closed. The
blower motor BLWM will transition to low-heat airflow five
seconds after the R-to-W2 circuit opens.
3. Cooling mode
The thermostat “calls for cooling.”
a. Single-Speed Cooling-
See Fig. for thermostat connections
The thermostat closes the R-to-G-and-Y circuits. The R-to- Y
circuit starts the outdoor unit, and the R-to-G-and-Y/Y2 circuits
start the furnace blower motor BLWM on cooling airflow.
Cooling airflow is based on the A/C selection shown in Fig. 14.
The electronic air cleaner terminal EAC-1 is energized with 115
vac when the blower motor BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y circuits are
opened. The outdoor unit will stop, and the furnace blower motor
BLWM will continue operating at cooling airflow for an
additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the
cooling off-delay to 5 seconds, see Fig. 35.
b. Single-Stage Thermostat and Two-Speed Cooling (Adaptive
Mode).
See Fig. for thermostat connections.
This furnace can operate a two-speed cooling unit with a
single-stage thermostat because the furnace control CPU
includes a programmed adaptive sequence of controlled
operation, which selects low-cooling or high-cooling operation.
This selection is based upon the stored history of the length of
previous cooling period of the single-stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be
connected to enable the adaptive cooling mode in response to a call for
cooling, see Fig. 35. When ACRDJ is in place the furnace control CPU
can turn on the air conditioning relay ACR to energize the Y/Y2 terminal
and switch the outdoor unit to high-cooling.
The furnace control CPU can start up the cooling unit in either low- or
high-cooling. If starting up in low-cooling, the furnace control CPU
determines the low-cooling on-time (from 0 to 20 minutes) which is
permitted before switching to high-cooling. If the power is interrupted,
the stored history is erased and the furnace control CPU will select
low-cooling for up to 20 minutes and then energize the air conditioning
relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to
high-cooling, as long as the thermostat continues to call for cooling.
Subsequent selection is based on stored history of the thermostat cycle
times.
The wall thermostat “calls for cooling”, closing the R-to-G-and-Y
circuits. The R-to-Y1 circuit starts the outdoor unit on low-cooling
speed, and the R-to-G-and-Y1 circuits starts the furnace blower motor
BLWM at low-cooling airflow which is the true on-board CF selection,
see Fig. 14.
If the furnace control CPU switches from low-cooling to high-cooling,
the furnace control CPU will energize the air conditioning relay ACR.
When the air conditioning relay ACR is energized the R-to-Y1-and-Y2
circuits switch the outdoor unit to high-cooling speed, and the
R-to-G-and-Y1-and-Y/Y2 circuits transition the furnace blower motor
BLWM to high-cooling airflow. High-cooling airflow is based on the
A/C selection, see Fig. 14.
NOTE: When transitioning from low-cooling to high-cooling the
outdoor unit compressor will shut down for 1 minute while the furnace
blower motor BLWM transitions to run at high-cooling airflow.
The electronic air cleaner terminal EAC-1 is energized with 115 vac
whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y circuit are opened.
The outdoor unit stops, and the furnace blower BLWM and electronic air
cleaner terminal EAC-1 will remain energized for an additional 90
seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5
seconds, see Fig. 35.
c. Two-Stage Thermostat and Two-Speed Cooling
See Fig. 34 for thermostat connections
NOTE: The air conditioning relay disable jumper ACRDJ must be
disconnected to allow thermostat control of the outdoor unit staging, see
Fig. 35.
d. The thermostat closes the R-to-G-and-Y1 circuits for
low-cooling or closes the R-to-G-and-Y1-and-Y2 circuits for
high-cooling. The R-to-Y1 circuit starts the outdoor unit on
low-cooling speed, and the R-to-G-and-Y1 circuit starts the
furnace blower motor BLWM at low-cooling airflow which is the
true on-board CF (continuous fan) selection, see Fig. 14. The
R-to-Y1-and-Y2 circuits start the outdoor unit on high-cooling
speed, and the R-to-G-and-Y/Y2 circuits start the furnace blower
motor BLWM at high-cooling airflow. High-cooling airflow is
based on the A/C (air conditioning) selection, see Fig. 14.
The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y1 or R-to-
G-and-Y1-and-Y2 circuits are opened. The outdoor unit stops,
and the furnace blower BLWM and electronic air cleaner
terminal EAC-1 will remain energized for an additional 90
seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to
5 seconds, see Fig. 35.
4. Dehumidify Mode
See Fig. 28 - Fig. 34 for thermostat connections.
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
45
The dehumidification output, DHUM on the Thermostat should be
connected to the furnace control thermostat terminal DHUM. When
there is a dehumidify demand, the DHUM input is activated, which
means 24 vac signal is removed from the DHUM input terminal. In
other words, the DHUM input logic is reversed. The DHUM input
is turned ON when no dehumidify demand exists. Once 24 vac is
detected by the furnace control on the DHUM input, the furnace
control operates in dehumidify mode. If the DHUM input is low for
more than 48 hours, the furnace control reverts back to
non-dehumidify mode.
The cooling operation described in item 3. above also applies to
operation with a thermostat. The exceptions are listed below:
a. Low cooling-When the R-to-G-and-Y1 circuit is closed and
there is a demand for dehumidification, the furnace blower motor
BLWM will drop the blower airflow to 86 percent of low-cooling
airflow which is the true on-board CF (continuous fan) selection,
see Fig. 14.
b. High cooling-When the R-to-G-and Y/Y2 circuit is closed and
there is a demand for dehumidification, the furnace blower motor
BLWM will drop the blower airflow to 86 percent of
high-cooling airflow. High-cooling airflow is based on the A/C
(air conditioning) selection, see Fig. 14.
c. Cooling off-delay-When the “call for cooling” is satisfied and
there is a demand for dehumidification, the cooling blower-off
delay is decreased from 90 seconds to 5 seconds.
5. Super-Dehumidify Mode
Super-Dehumidify mode can only be entered if the furnace control
is in the Dehumidify mode and there is a demand for
dehumidification. The cooling operation described in item 3. above
also applies to operation with a thermostat. The exceptions are
listed below:
a. When the R-to-Y1 circuit is closed, R-to-G circuit is open, and
there is a demand for dehumidification, the furnace blower motor
BLWM will drop the blower airflow to 65 percent of low-cooling
airflow for a maximum of 10 minutes each cooling cycle or until
the R-to-G circuit closes or the demand for dehumidification is
satisfied. Low-cooling airflow is the true on-board CF
(continuous fan) selection, see Fig. 14.
b. When the R-to-Y/Y2 circuit is closed, R-to-G circuit is open, and
there is a demand for dehumidification, the furnace blower motor
BLWM will drop the blower airflow to 65 percent of
high-cooling airflow for a maximum of 10 minutes each cooling
cycle or until the R-to-G circuit closes or the demand for
dehumidification is satisfied. High-cooling airflow is based on
the A/C (air conditioning) selection, see Fig. 14.
c. When the “call for cooling” is satisfied and there is a demand for
dehumidification, the cooling blower-off delay is decreased from
90 seconds to 5 seconds.
6. Continuous Blower Mode
When the R-to-G circuit is closed by the thermostat, the blower
motor BLWM will operate at continuous blower airflow.
Continuous blower airflow selection is initially based on the CF
(continuous fan) selection, see Fig. 14. (The factory default is
shown in Fig. 14. Terminal EAC-1 is energized as long as the
blower motor BLWM is energized.
During a call for heat, the furnace control CPU will transition the
blower motor BLWM to continuous blower airflow, low-heat
airflow, or the mid-range airflow, whichever is lowest. The blower
motor BLWM will remain ON until the main burners ignite then
shut OFF and remain OFF for the blower-ON delay (45 seconds in
low-heat, and 25 seconds in high-heat), allowing the furnace heat
exchangers to heat up more quickly, then restarts at the end of the
blower-ON delay period at low-heat or high-heat airflow,
respectively.
The blower motor BLWM will revert to continuous-blower airflow
after the heating cycle is completed. In high-heat, the furnace
control CPU will drop the blower motor BLWM to low-heat airflow
during the selected blower-OFF delay period before transitioning to
continuous-blower airflow.
When the thermostat “calls for low-cooling”, the blower motor
BLWM will switch to operate at low-cooling airflow. When the
thermostat is satisfied, the blower motor BLWM will operate an
additional 90 seconds at low-cooling airflow before transitioning
back to continuous-blower airflow.
When the thermostat “calls for high-cooling”, the blower motor
BLWM will operate at high cooling airflow. When the thermostat is
satisfied, the blower motor BLWM will operate an additional 90
seconds at high-cooling airflow before transitioning back to
continuous-blower airflow. When the R-to-G circuit is opened, the
blower motor BLWM will continue operating for an additional 5
seconds, if no other function requires blower motor BLWM
operation.
Continuous Blower Speed Selection from Thermostat
To select different continuous-blower airflow from the room thermostat,
momentarily turn off the FAN switch or push button on the room
thermostat for 1-3 seconds after the blower motor BLWM is operating.
The furnace control CPU will shift the continuous-blower airflow from
the factory setting to the next highest CF selection airflow, see Fig. 14.
Momentarily turning off the FAN switch again at the thermostat will
shift the continuous-blower airflow up one more increment. If you repeat
this procedure enough you will eventually shift the continuous-blower
airflow to the lowest CF selection, see Fig. 14. The selection can be
changed as many times as desired and is stored in the memory to be
automatically used following a power interruption.
NOTE: If the blower-off delay is set to the maximum, the adjustable
continuous-fan feature is locked (i.e., fan speed cannot be changed from
its current setting).
7. Heat pump
See Fig. 32 - Fig. 33for thermostat connections.
When installed with a heat pump, the furnace control automatically
changes the timing sequence to avoid long blower off times during
demand defrost cycles. Whenever W/W1 is energized along with
Y1 or Y/Y2, the furnace control CPU will transition to or bring on
the blower motor BLWM at cooling airflow, low-heat airflow, or
the mid-range airflow, whichever is lowest. The blower motor
BLWM will remain on until the main burners ignite then shut OFF
and remain OFF for 25 seconds before coming back on at heating
airflow. When the W/W1 input signal disappears, the furnace
control begins a normal inducer post-purge period while changing
the blower airflow. If Y/Y2 input is still energized the furnace
control CPU will transition the blower motor BLWM airflow to
cooling airflow. If Y/Y2 input signal disappears and the Y1 input is
still energized the furnace control CPU will transition the blower
motor BLWM to low-cooling airflow. If both the Y1 and Y/Y2
signals disappear at the same time, the blower motor BLWM will
remain on at low-heat airflow for the selected blower-OFF delay
period. At the end of the blower- OFF delay, the blower motor
BLWM will shut OFF unless G is still energized, in which case the
blower motor BLWM will operate at continuous blower airflow.
8. Component test
The furnace features a component test system to help diagnose a
system problem in the case of a component failure. To initiate the
component test procedure, ensure that there are no thermostat
inputs to the control and all time delays have expired. Turn on setup
switch SW1-6, see Fig. 35..
NOTE: The component test feature will not operate if the control is
receiving any thermostat signals or until all time delays have expired.
The component test sequence is as follows:
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
46
a. The furnace control CPU turns the inducer motor ON at
high-heat speed and keeps it ON through step c.
b. After waiting 10 seconds the furnace control CPU turns the hot
surface igniter ON for 15 seconds, then OFF.
c. The furnace control CPU then turns the blower motor BLWM on
at mid-range airflow for 15 seconds, then OFF.
d. After shutting the blower motor OFF the furnace control CPU
switches the inducer to low-heat speed for 10 seconds, then OFF.
NOTE: The EAC terminals are energized when the blower is operating.
After the component test is completed, 1 or more status codes (11, 25 or
41) will show. See component test section or Service Label (Fig. 52) for
explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1-6 to OFF and
then back ON.
Wiring Diagram
Refer to Fig. 56 for wiring diagram.
Troubleshooting
Refer to the service label (see Fig. 52) for some troubleshooting
information. Also, the Troubleshooting Guide (see Fig. 57) can be a
useful tool in isolating furnace operation problems. Beginning with the
word “Start,” answer each question and follow the appropriate arrow to
the next item. The Guide will help to identify the problem or failed
component. After replacing any component, verify correct operation
sequence.
WIRING DIAGRAM
A210194
Fig. 56 – Wiring Diagram
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
47
TROUBLESHOOTING GUIDE
A02108A
Is AMBER LED status light blinking ON/OFF
slowly with a combination of short and
long flashes?
Is AMBER LED status
light blinking
rapidly w
ithout a pause?
Is AMBER LED status
light on?
Determine status code. The status code is
a 2 digit number with the first digit determined
by the num
ber of shor
t flashes and the
second digit by the number of long flashes?
Go to section below for the status code
that was flashed.
YES
NO
YES
To recall previous status codes disconnect
the R thermostat connection, reset power,
and put setup switch SW
1-1
in the ON
position. The AM
BER LED w
ill flash the
status codes in the order of occurrence.
Record status codes until status code #11
flashes (1 short and 1 long flash). After status
code #11 flashes the status codes will repeat.
Status codes are erased after 72 hours or
can be m
a
nually erased by putting setup
s
witch SW
1-1
in the O
N position and
jumpering R, W/W1, and Y/Y2 simultaneousl
y
until status code #11 is flashed. When done
put setup switch SW1-1 in the O
FF posi
tion.
Check for correct line voltage polarity.
If units are twinned, check for proper
low-voltage (24V) transformer phasing.
Was there a previous status code other
than #11?
Is door switch closed?
Is there 115V going to switch?
Replace door switch.
Replace transformer.
Does the control respond to W/W1, W2, Y1,
Y/Y2, and G (24V) thermostat signals?
Replace furnace control.
NO
NO
NO
NO
Is 24V present at W/W1, W2, Y1, Y/Y2 or G
thermostat terminals on the
fur
nace control?
NO
YES
YES
Replace furnace control.
Is there 24V at SEC-1 and SEC-2?
Is there 115V at L1 and L2?
YES
NO
YES
YES
NO
YES
NO
YES
Run system
through a
lo
w-heat, high-heat,
or cooling cycle to check operation. Status
codes are erased after 72 hours or can be
manually erase
d b
y putting setup switch
SW1-1 in the ON position and jumpering R,
W/W1, and Y/Y2 sim
ultaneou
sly until status
code #11 is flashed.
YES
NO
Close circuit break
er and go back to START.
Check for continuity in wire from
circui
t
breaker to furnace.
Is circuit breaker closed?
Is door switch closed?
Check room thermostat or
interconnecting cable.
NO
YES
YES
NO
The thermostat is not com
patib
le with the
furnace control. Either install a ballast resistor,
connect the Com24V
thermostat terminal to
the thermostat, or replace the thermostat.
Does the problem repeat w
hen using
a jumper wire?
Disconnect all the thermostat wires from the
furnace control.
START
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
48
A02108B
11 NO PREVIOUS CODE – Status codes
are erased after 72 hours or can be
manually erased by putting setup switch
SW1-1 in the ON position and jumpering
R, W/W1, and Y/Y2 simultaneously until
status code #11 is flashed. Run system
through a low-heat, high-heat, or cooling
cycle to check system.
12 BLOWER ON AFTER POWER UP –
(115V OR 24V) – Normal operation.
Blower runs for 90 seconds, if unit is
powered up during a call for heat (R-
W/W1 closed) or when (R-W/W1 opens)
during the blower on-delay period.
13 LIMIT CIRCUIT LOCKOUT – Lockout
occurs if the limit, draft safeguard, flame
rollout, or blocked vent switch* (if used)
is open longer than 3 minutes or 10
successive limit trips occurred during
high-heat. Control will auto-reset after 3
hours. See code 33.
14 IGNITION LOCKOUT – System failed to
ignite gas and prove flame in 4 attempts.
Control will auto-reset after 3 hours.
See status code 34.
15 BLOWER MOTOR LOCKOUT – Indicates
the blower failed to reach 250 RPM or
the blower failed to communicate within
30 seconds after being turned ON in two
successive heating cycles. Control will
auto-reset after 3 hours. See code 41.
21 GAS HEATING LOCKOUT – Turn off
power and wait 5 minutes to retry.
Check for:
- Stuck closed gas valve relay on control.
- Miswire or short to gas valve wire.
22 ABNORMAL FLAME-PROVING SIGNAL
Flame is proved while gas valve is de-
energized. Inducer will run until fault is
cleared. Check for:
- Stuck open or leaky gas valve.
23 PRESSURE SWITCH DID NOT OPEN
Check for:
- Obstructed pressure tube.
- Pressure switch stuck closed.
24 SECONDARY VOLTAGE FUSE IS OPEN
Check for:
- Short circuit in secondary voltage
(24V) wiring including thermostat
leads. Disconnect thermostat leads
to isolate short circuit.
32 LOW-HEAT PRESSURE SWITCH DID
NOT CLOSE OR REOPENED – If open
longer than 5 minutes, inducer shuts off
for 15 minutes before retry. If opens
during blower on-delay period, blower will
come on for the selected blower off-delay.
Check for:
- Proper vent sizing.
- Low inducer voltage (115V).
- Low inlet gas pressure (if LGPS used).
- Inadequate combustion air supply.
- Disconnected or obstructed pressure
tubing.
-
Defective inducer motor.
- Defective pressure switch.
- Excessive wind.
- Restricted vent.
33 LIMIT CIRCUIT FAULT – Indicates the
limit, draft safeguard, flame rollout, or
blocked vent switch* (if used) is open or
the furnace is operating in high-heat only
mode due to 2 successive low-heat limit
trips. Blower will run for 4 min. or until
open switch remakes whichever is longer.
If open longer than 3 min., code changes
to lockout #13. If open less than 3 min.
status code #33 continues to flash until
blower shuts off. Flame rollout switch and
BVSS requires manual reset. Check for:
-Dirty filter or restricted duct system.
- Loose blower wheel.
- Defective switch or connections.
- Inadequate combustion air supply
(flame rollout switch open).
- Restricted vent.
- Proper vent sizing.
- Excessive wind.
34 IGNITION PROVING FAILURE – If flame
is not sensed during the trial for ignition
period, the control will repeat the ignition
sequence 3 more times before lockout
#14 occurs. If flame signal is lost during
the blower on-delay period, blower will
come on for the selected blower off-delay.
Check the following items first before
proceeding to the next step.
- Gas valve turned off.
- Manual shut-off valve.
- Green/Yellow wire MUST be connected
to furnace sheet metal.
- Flame sensor must not be grounded.
To determine whether the problem is in
the gas valve, igniter, or flame sensor the
system can be operated in component
test mode. To check the igniter remove
the R thermostat connection from the
control, reset power, and put setup switch
SW1-6 in the ON position to start the
component test. Does the igniter glow
orange/white by the end of the 15 second
warm-up period?
43 LOW-HEAT PRESSURE SWITCH OPEN
WHILE HIGH-HEAT PRESSURE
SWITCH IS CLOSED - Check for:
-Low-heat pressure switch stuck open.
- Disconnected or obstructed pressure
tube.
- Miswired pressure switches.
-Low inlet gas pressure (if LGPS used).
Unplug igniter harness from control and
repeat component test by
turning setup s
witch
SW1-6 OFF and then back ON. Check for
115V between pin 3 and NEUTRAL-L2 on
the control. Was 115V present for the 15
second period?
Reconnect the R thermostat lead and set
thermostat to call for heat. Connect voltmeter
across gas valve connections. Does gas
valve receive 24V?
Does gas valve open and allow gas to flow?
Do the main burners ignite?
Do the main burners stay on?
Repeat call for heat and check flame sensor
current during trial for ignition period. Is the
DC microamps below 0.5?
Clean flame sensor with fine steel wool and
recheck current. Nominal current is 4.0 to
6.0 microamps.
Is current near typical value?
Will main burners ignite and stay on?
Fixed.
45 CONTROL CIRCUITRY LOCKOUT
Auto-reset after 1 hour lockout due to:
- Flame circuit failure.
- Gas valve relay stuck open.
- Software check error.
Reset power to clear lockout.
Replace control if code repeats.
Replace furnace control.
Check for continuity in the harness and
igniter. Replace defective component.
YES
NO
YES
YES
YES
NO
YES
Check connections
. If OK, replace control.
Check that all gas valves are turned on.
Replace valve.
Check for:
- Inadequate flame carryover or rough
ignition.
-Low inlet gas pressure.
-Proper firing rate.
-Blocked or incorrect carry- over gap.
(.045” nominal)
Allow blower to come on and repeat test
to check for intermittent operation.
Check connections and retry. If current is
near typical value (4.0-6.0 nominal) and
burners will not stay on, repeat check in high-
heat. If burners will still not stay on replace
control. If burners operate in high-heat then
switch to low-heat,check manifold pressure.
If OK, check burner carryover and flame
sensor location.
Replace electrode.
Replace furnace control.
NO
NO
NO
YES
NO
NO
NO
NO
YES
* Blocked vent switch used in C
himn
ey Adapter Kit
YES
YES
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
49
A02108C
Fig. 57 – Troubleshooting Guide
25 INVALID MODEL SELECTION OR
SETUP
ERRORIf status code 25 only
flashes 4 tim
es on po
wer-up the control
is missing its m
odel plug
PL4 and is
defaulting to
the model
selection sto
red
in memor
y. If statu
s code 25 fla
shes
contin
uously it could ind
icate any of the
following:
- Model p
lug PL4 is m
issing
and there
is no valid m
odel stored in per
manent
memory. This will happen if you forget
to install the m
odel plug P
L4 on a
service replace
ment contro
l.
-T
hermostat ca
ll with SW1-1 ON.
-Thermostat ca
ll with SW1-6 ON.
-SW1-1 and S
W1-6 both O
N.
31 HIGH-HEA
T PRESSURE SWITCH OR
RELAY DID NO
T CLOSE OR
REOPENED - Chec
k for:
-C
ontrol relay may be d
ef
ective.
- Gas valve is mis
wired.
-See status code 3
2.
41 BLOWER MOTOR FAULT – Indicates the
blo
wer failed to reach 2
50 RPM or th
e
blower failed to com
municate w
i
thin the
prescribed tim
e limits
. Thirty seconds
after being tu
r
ned ON or ten seco
nds
during steady-state operation. Turn power
off and check the following item
s first
before proceed
ing to the
ne
xt step.
-Rubbing blower wheel.
-Loose blower wheel.
-Wiring from
fur
nace control to b
lower
motor.
Remo
v
e the R
ther
mostat conn
ection
from the furnace control, disconnect both
connectors fro
m the b
lower motor P
L13
and PL14.
Does the blower wheel tur
n
freely?
Replace
the b
lower control m
odule at
tached
to the blower motor
. Follow the in
structions
with the blower control m
odule to
make sure
the entire blower motor does not n
e
ed to be
replaced.
You have an open w
ire or bad ter
minal on the
BLUE wire betwe
en the furnace con
trol and
the blo
wer motor
.
Replace the fu
r
nace control.
Connect a D
C v
oltmeter across PL3-4 B
LU
E
(+) and
PL3-2
GREEN (-).
Does the
v
oltage
fluctuate
as de
scribed two steps
back?
Does the voltage fluctuate as described in the
previous ste
p?
Replace the blower control m
odule atta
ched
to the blower motor. Follow the instructions
with the blower control m
odule to mak
e sure
the
entire
b
lo
wer motor does
not need to be
replaced.
Turn power back on. Is there
115V
AC at
PL14-5 and P
L14-4?
Is there 12-VDC
at PL13-7 RED (+) and PL13-
1 GREEN (-)?
Is there 12-V
DC at PL3-
1 RED (+) and P
L3-
2 GREEN (-)?
Replace
the fur
nace control.
Is there 5-VDC a
t PL13-16 YELLOW (+) and
PL13-1
GREEN (-)?
The voltage just m
easured
should be v
er
y
stable and
should not flu
ctuate m
ore tha
n
.02-VDC
. If the
voltage fluctuates more than
this get a diff
erent voltmeter before
proceeding.
Turn power off, reconnect PL13 and PL14
to
the blower motor
, then tur
n power back on.
Connect a D
C v
oltmeter acro
ss PL3-3
YELLOW (+) and
PL3-2 G
REEN (-).
Does
the voltage
fluctuat
e more tha
n it
did in the
pre
vious step?
Turn power off, disconnect P
L13 and PL14
from the blower motor, then turn power back
on. Connect a D
C
voltmeter a
cross PL1
3-
16 BLUE (+) an
d PL13-1 G
REE
N (-). The
voltage sho
uld be
near 0-VDC b
ut it wil
l
fluctuate briefly several times a second.
If
you have an analog voltmeter the
needle will
briefly go high several times a second. If you
have a dig
ital v
oltmeter w
ith
a bar graph it
will sho
w a large chan
ge
in magnitude on
the bar graph several tim
es
a second.
If you
have a standard digital voltmeter
it will show
a brief fluctuation in voltage and the
magnitude m
a
y vary dep
ending on th
e
voltmeter used.
Yo u have an open w
ire or b
a
d terminal on
either the B
LA
CK or WHITE po
wer leads
between the furnace contro
l and the b
lower
motor. If you have a power choke disconnect
it and chec
k continuity.
You have an open
wire or ba
d terminal on
either the R
ED or GREEN wire between
th
e
furnace contro
l and the b
lo
wer motor
.
Is there 5-V
DC at PL3-3
YELLO
W (+) and
PL3-2 GREEN (-)?
You have an open wire or bad terminal on the
YELLOW wire between the fur
nace control
and the blower motor
.
YES
NO
NO
NO
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
YES
YES
NO
©2021 Carrier. All rights reserved.
A Carrier Company
Edition Date: 08/21
Catalog No: II880TA-02 REV A
Replaces: II880TA-02
880TA/881TA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
50
PARTS REPLACEMENT INFORMATION GUIDE
CASING GROUP
Outer door
Blower door
Top filler plate
Bottom filler plate
Bottom enclosure
ELECTRICAL GROUP
Control bracket
Junction box
Limit switch(es)
Circuit board
Door switch
Transformer
Wiring harness 115v
Wiring harness 24v
BLOWER GROUP
Blower housing
Blower cutoff
Blower motor
Blower wheel grommet
GAS CONTROL GROUP
Manifold
Burner assembly
Orifice
Flame sensor
Hot surface igniter
Gas valve
Manual reset limit switches
Burner support assembly
HEAT EXCHANGER GROUP
Heat exchanger cell
Cell panel
Lox NOx baffle (California models only)
INDUCER GROUP
Housing assembly
Pressure switch
Inducer motor
Inducer wheel
Vent elbow assembly
Draft safeguard switch
Power choke (where used)
TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or classified section of your local telephone directory under “Heating
Equipment” or “Air Conditioning Contractors and Systems” headings for dealer listing by brand name or contact:
BRYANT HEATING & COOLING SYSTEMS
Consumer Relations Department
P.O. Box 4952
Syracuse, New York 13221-4952
1-800-428-4326
EXAMPLE OF MODEL NUMBER
TRAINING
My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses. We
believe in providing high quality learning experiences both online and in the classroom.
Access My Learning Center with your HVACpartners credentials at www.mlctraining.com.
Please contact us a mylearning@carrier.com with questions.
MODEL
COOLING
CAPACITY
HEATING
CAPACITY
MOTOR WIDTH VOLTAGE
FEATURES/
MINOR SERIES
880TA 36 045 E 17 A -A
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, personal injury, death or property damage.
Improper installation, adjustment, alteration, service, or maintenance can cause personal injury, property damage, or death. Consult a qualified installer, service agency,
or your local gas supplier for information or assistance. The qualified installer or service agency must use only factory-authorized replacement parts, kits, or accessories
when modifying this product.
WARNING
!