INSTALLATION INSTRUCTIONS
IMPORTANT
CONTROL MOUNTING
Mount the ETC to a wall or any at surface using a combination
of any two or more of the slots located on the back case anges.
The control’s components are not position sensitive, but should
be mounted so that they can be easily wired and adjusted.
Avoid excessive conditions of moisture, dirt, dust and corrosive
atmosphere during installation.
The ETC NEMA Type 4X control has provisions for a 1/2 inch
conduit connection. The conduit hub should be secured to the
conduit before securing the hub to the plastic housing of the
control. Caution should be exercised not the damage the control
circuit board or wiring when installing a conduit connector.
Installation of ETC NEMA Type 4X controls must conform to
requirements of the National Electrical Code and Canadian
Standards Association. Conduit ttings must be listed by
Underwriters Laboratories and Canadian Standards Association
as “Liquid-Tight” when installed to the manufacturer’s
specications.
CAUTION
To prevent possible electrical shock or equipment damage,
disconnect electrical power to the unit before and during
installation. DO NOT restore electrical power to the unit until
the control is properly installed and the cover is assembled.
DO NOT locate the control in an explosive atmosphere as a
safety hazard can result due to possible spark generation in
the control. Use the control in such environments may result in
injury or damage to the persons or property (or both) and are
likely to shorten control life;
Invensys Controls assumes no responsibility for any
such use.
CONTROL WIRING
General
• All wiring should conform to the National Electric Code and
local regulations.
• The total electrical load must not exceed the maximum
rating of the control (see Specications).
• Use copper conductors only.
• Electrical leads should not be taut; allow slack for temperature
change and vibration.
Input and Output Wiring
For typical wiring diagrams, refer to Figures 4 and 5.
All connections are made to the power (lower) circuit board.
Sensor Wiring
The temperature sensor leads are soldered to the circuit board
so no additional connections are necessary. However, watertight
splicing is required when extending the sensor cable length
beyond the standard 25 foot length supplied with the ETC. The
sensor cable can be extended up to 400 feet. A clip is included
for mounting the sensor bulb.
The ETC sensor should not be immersed directly in water or any
other uid. For immersion applications, the sensor should be
placed in a thermowell. For best results, use thermal grease in the
well to assure faster response to the sensed uid temperature.
A damaged sensor can be replaced by splicing a new Invensys
Control sensor onto the sensor leads from the circuit board. The
sensor is not polarity sensitive.
SET
Electronic
Temperature
Control
NEMA TYPE 4X
OUTDOOR ENCLOSURE
7.00
7.53 7.83
FRONT VIEW
2.00
2.70
0.99
0.88 DIA HOLE
FOR 0.50 DIA. CONDUIT
SIDE VIEW
6.52
2.48
0.13
BOTTOM VIEW
1.
All ETC series controls are designed as operating controls
only. If an operating control failure could result in personal
injury or loss of property, a separate safety control and/or
alarm should be installed.
2.
The schematic drawings and other information included
in these installation instructions are for the purpose of
illustration and general reference only.
3.
These instructions do not expand, reduce, modify or alter
the Invensys Controls Terms in any way; and no warranty
or remedy in favor of the customer or any other person
arises out of these instructions.
4.
Ranco ETC controls have been approved by Underwriter’s
Laboratories as UL Listed; however, approval does not
extend to their use for any other purpose. Invensys
Controls assumes no responsibility for any unconventional
application of its control unless such application has been
approved in writing by Invensys Controls.
5.
It is the responsibility of the installer and the user to
assure that his or its application and use of all Invensys
Controls products are in compliance with all federal, state
and local requirements, including, without any limitation,
all requirements imposed under the National Electric Code
and any applicable building codes.
3
Figure 3